Cable Management
External influences O
Jake Green, head of technical engagement, Scolmore Group, gives a brief overview of the general range of conditions detailed in Section 522 of BS 7671, which an installer will have to consider as they select a suitable wiring system for an electrical installation.
ne of the fundamental principles detailed in Chapter 13 of BS 7671: 2018 (including amendments) is ‘Environmental conditions’. Simply stated, Regulation 132.5.1 requires that ‘the design of the electrical installation shall take into account the environmental conditions to which it will be subjected’.
Section 522
Section 522 of BS 7671 details those environmental conditions that need to be considered when selecting and installing wiring systems. The scope of the section is wide ranging covering the following: Ambient temperature – requires the designer/ installer to ensure that installed equipment is suitable for both the minimum and maximum temperatures reasonably expected. Account should also be taken of the maximum temperature expected under fault conditions (522.1). External heat sources – electrical equipment must be protected from the detrimental effects of specific heat sources. This might be by shielding, distancing from the source, having equipment capable of managing the level of heat or local reinforcement or substitution of insulating material (522.2).
Presence of water or high humidity – electrical equipment must be suitably protected from ingress by water and/or the build-up of condensation. The Unicrimp Q-Nect series (junction boxes, connectors and connection boxes) provides a range of IP66 to IP68 products, providing the designer/installer with suitable options when selecting equipment for use in the presence of water (522.3).
Presence of solid foreign bodies – requires the wiring system to be capable of minimising the danger arising from the ingress of solid foreign bodies. The IP rating should be suitable for the nature of the foreign bodies (522.4). Presence of corrosive or polluting substances – requires due account to be taken of materials/substances likely to cause corrosion or deterioration of the wiring system. This can be water (rust), presence of dissimilar metals or more obvious corrosive substances (522.5). Impact – the wiring system must be capable of withstanding damage caused by mechanical
stress such as, impact, abrasion, penetration, tension, compression during installation as well as being protected from impact as part of the fixed installation (522.6). Vibration – requires a wiring system to be supported in such a way that due account is given to the likely vibration that will exist. This may require, for example, use to be made of
saddle clips rather than standard cable clips where a cable is not installed within a cable management system (522.7). Other mechanical stresses – requires a wiring system to be selected and erected to avoid during installation, use or maintenance, damage to the sheath. This requires use to be made, where necessary of correct saddles, clips
28 | electrical wholesaler June 2024
ewnews.co.uk
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44