Fire protection enclosures contribute to the safety of Limbecker Platz mall


In the event of fire in large, crowded shopping centres, the safety and well-being of anyone inside relies on emergency systems operating for long enough for people to escape. Limbecker Platz, one of the largest shopping centres in Germany, chose Spelsberg’s WKE enclosures to provide adequate fire safety protection to vital circuitry that can save lives in the event of fire


W


hile fire prevention plans have greatly contributed to minimise the likelihood of a fire happening in public buildings such as airports, hospitals and shops, the risk cannot be completely eliminated. The percentage of fires in the UK’s shopping centres accounts for 1.7 per cent of the country’s retail fires, which are estimated to be 10.5 per cent of all large loss fires in the UK, according to the Fire Protection Association and the RISCAuthority Large Loss Fire database. The data provided also indicates that the likelihood of fires in malls is equally distributed throughout the day, i.e. the event has the same probability of occurring during a shopping centre’s opening or closing times. Therefore, fire safety is essential and should be supported at all times. In particular, the electrical equipment that supports emergency systems must be adequately protected in the event of fire. In fact, in the event of a fire, electrical systems such as lighting, ventilation, smoke extraction and suppression are vital for saving lives. These systems must be protected from the force of the fire and remain operational long enough for thousands of people to be safely evacuated and for firefighters to extinguish the fire. A shopping centre that has been successful in implementing state-of-the-art fire safety equipment is Limbecker Platz. Built in 2008 and located in Essen, Germany, the mall contains more than 140 retail shops and 25 restaurants across its


70,000m2 of floor area. With a daily foot traffic of over 50,000 people, the mall requires the highest standards of management to ensure that risks, including fires, are anticipated and covered. Alexandra Wagner, center manager at Limbecker Platz explained: “We feel responsible for the safety of our visitors and tenants, and we aim to be well- prepared in case of a real emergency.”


Enclosures for optimal electrical functional integrity In order to ensure that electrical installations for emergency systems function safely during a fire, mall managers have to choose between two standard methods of providing fire protection to electrical circuits. The first one consists in encasing the conduits in concrete, mostly within walls; while the second option involves cabling and enclosures that can withstand fire for a prolonged amount of time. The first method presents some limitations. First, it is necessary to design the encasement before the building is erected, therefore any modernisation, inspection or maintenance would require the demolition of the original concrete encasement. Second, while the concrete encasement protects against flame passage, there is no standard identifying how long different concretes may protect an electrical circuit from failure. Finally, this design does not allow for access or visual inspection of conduits and cables should a problem present itself in day-to-day operation.


Despite the high quality of fire


protection afforded by this option, in many cases the expense and impracticalities make concrete encasement an unviable option. Having reviewed their options, the mall managers at Limbecker Platz chose to follow the second option of specifying fire resistant cabling and enclosures.


Solutions that adhere to stringent fire safety regulations are key The next challenge for Limbecker Platz’s managers consisted in finding suitable equipment that would comply with the German standard DIN 4102-12 “Fire behaviour of building materials and elements – Fire resistance of electric cable systems required to maintain circuit integrity – Requirements and testing”. This regulation is considered one of the strictest in Europe and requires all the components of an entire cable system to withstand temperatures of up to 1,000°C and remain operational for at least 30, 60 or 90 minutes. The minimum duration for functional integrity of electrical systems is expressed as an ‘E’ followed by the number of minutes of functional integrity. For example, E60 indicates that the enclosure can resist fire for a minimum of 60 minutes. The intrinsic fire resistance of the electrical components allows the people inside to leave the building and rescue forces to operate. In addition to DIN 4102-12, the installations must adhere to the European EN 60670 standard “Boxes and enclosures for electrical accessories for household and similar fixed electrical installations. General requirements”, which provides a number of environmental requirements. For example, the electrical enclosure should feature protection against moisture, dust, corrosion and mechanical stress. Ingress protection classification, in turn, is regulated by the DIN EN 60529 (VDE 0470). In order to address the relevant


regulations, the electrical installers for the Limbecker Platz mall project chose to rely on one of the world’s leading manufacturers of electrical equipment enclosures and distribution boards: Spelsberg. Chris Lloyd, managing director at Spelsberg, commented: “We are


18 March 2019 Components in Electronics


committed to deliver high-quality fire protection enclosures that support businesses like Limbecker Platz and align with their fire protection policies. The safety measures within the mall are advanced, and we are happy to play a part in protecting its visitors and personnel with our quality solutions.” With a long tradition of technical innovation and quality products, Spelsberg manufactures its WKE fire protection enclosures in accordance with DIN 4102- 12, i.e. guarantees electrical functional integrity for 30, 60 up to 90 minutes in the event of a fire. Also, Spelsberg’s solutions are certified according to EN 60670 and EN 60529, thus provide different degrees of ingress protection against dust and water ingress, from IP54 up to IP67.


A winning product for fire safety The boxes, which can be customised in order to address specific customer requirements, are made of Duroplast, which is an extremely robust, halogen-free, fibre-reinforced, thermosetting plastic. When heated, the material becomes irreversibly rigid - instead of melting - and offers low smoke emissions. The WKE solution is therefore heat and fire resistant. In addition, the junction boxes prevent the penetration of foreign objects and offer further durability in conditions of extreme heat by means of pre-fitted ceramic terminals as standard. Spelsberg’s products are all tested and certified according to the VDE and the Material Testing Institute (MPA). The company’s in-house laboratory can carry out VDE-compliant testing for certifications. The facilities are subject to an annual system audit by VDE to confirm adherence to the required specification. The resulting electrical installation is now


providing the Essen shopping centre and its visitors with a cost-effective, reliable and easy to maintain fire risk management solution. According to the fire department, the shopping centre is well prepared in the event of an emergency. This result attests to the high quality of the fire protection equipment system.


www.spelsberg.co.uk www.cieonline.co.uk


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52