MAKING THE RIGHT CHOICE Weighing up water heater protection


Water heater protection is important to ensure safe hot water generation. Apart from the Legionella risk, which is best managed by hot water storage at or above 60°C, corrosion is another issue. So how can you protect water heaters and what effect does the environment have on them? Kevin Potter, Business Development Manager for Hot Water Solutions at Hamworthy Heating, explains.


High water temperatures, levels of oxygen, and acidity, all act as reaction promoters, creating ‘ideal’ conditions for corrosion to develop.


M


To prevent this in the first place, a porcelain enamel lining is applied to the inside of the vessel. Hence, the hot water’s contact point is the lining rather than the steel shell itself. However, despite careful manufacturing processes, microscopic cracks in the lining are not completely preventable. These small areas may expose the steel lining to the hot water with an opportunity for corrosion to take hold.


A matter of protection dependent on water properties


The ideal method of protecting a water heater depends on the water hardness of the area it operates in. Hard water contains more dissolved mineral ions such as calcium and magnesium, which improves its conductivity. But why is this relevant?


Dependent on the manufacturer, enamel lined cylinders might be delivered with sacrificial anodes to prevent corrosion.


A sacrificial anode, by virtue of its name, ‘sacrifices’ itself for the benefit of the cylinder. The protection mechanism is based on an electrochemical process. Water serving as an electrolyte and the cylinder’s steel shell (less reactive metal) as the cathode, a magnesium (more reactive metal) anode is installed. The latter, once submerged in water, offers a target for oxidisation in lieu of the steel shell. The electrons that are freed during this corrosion process travel through the conductive medium (water) to the cathode (steel shell), reducing it to its elementary form, thereby protecting it. Referring to the higher concentration of dissolved mineral ions in hot water above and higher conductivity thereof means ideal conditions for the reaction and hence the protection of the cylinder.


These anodes require maintenance and due to the varying quality and chemical constitution of water, they corrode at different rates depending on the location. These area- specific factors form the basis for an assessment of the rate of deterioration and when regular inspection is required to check the state of the anodes.


However, not all areas of Great Britain have hard water. In fact, the North and West are characterised by soft water areas. How does this affect the anode?


ost common hot water cylinder shells are made of mild steel. Corrosion can occur when an electrochemical reaction between different metals used in the construction of water heaters (such as for the connections


etc) takes place. Soft water, fewer ions


The lower the number of dissolved metal ions, the lower the electrical conductivity, which is the case for soft water. This adversely affects the chemical reaction between sacrificial anode and cylinder shell, inhibiting protection. In these cases, when checked the anode often seems to be in excellent condition.


At the same time, however, this means it might not be working at all, putting the heater at risk. To bypass this problem, a powered anode can be used or a cylinder made from a different material selected.


A different case is hard water softened by the means of salt such as sodium chloride. Magnesium and calcium ions, which cause water to be ‘hard’, are substituted by the sodium ions which then ‘softens’ the water. The adverse effect of this method is increased conductivity which promotes corrosion. An example where this would naturally occur is in the ocean, where sea water corrodes ship wrecks quickly.


The powered alternative


A powered anode is non-sacrificial. Instead of the anode giving up its own electrons and producing an electrolytic current such as in the case of a sacrificial magnesium anode, an electrical supply produces a very low current in the water. This has the same protective effect on the cylinder’s steel shell, but without corroding the anode often made of titanium which will theoretically last the lifetime of the hot water cylinder.


However, a powered anode in certain soft water areas may still not have a protective effect, as the conductivity of the water, which the powered anode requires, is often poor.


What if neither powered nor sacrificial anodes are effective?


Corrosion-resistant stainless steel cylinders are often used in and suited for these parts of the UK: areas such as Scotland, South West and North West England, and west of Wales closer to the coast line. This gives peace of mind that the calorifier is being protected, as the user might not be aware of an installed anode not providing any. Whichever method of protection or type of cylinder is chosen, some form of maintenance is always required to ensure a safe and efficient hot water system. This reduces the risks of Legionella and scale forming within the system and prolongs the life of the product.


Making the right choice ‘


The ideal method of protecting a water heater depends on the water hardness of the area it operates in. Hard water contains more dissolved mineral ions such as calcium and magnesium, which improves its conductivity.


’ 16 BUILDING SERVICES & ENVIRONMENTAL ENGINEER NOVEMBER 2017


Each means of protection has its advantages. Sacrificial anodes require good conductivity of the water they operate in which makes them very effective for hard water areas. Powered anodes are a better choice for areas where water is softer and conductivity too low to produce its own current via sacrificial anode. These are also suitable for areas where water has been softened using salt, as the corrosion-promoting salinity causes sacrificial anodes to corrode too quickly.


In extremely low conductivity circumstances, however, corrosion-resistant stainless steel cylinders are a good choice which don’t require anode protection whatsoever.


www.hamworthy-heating.com VISIT OUR WEBSITE: www.bsee.co.uk


uSimplified illustration of a water heater. Electrons (red) move from the corroding magnesium anode (grey) to exposed areas of the cylinder’s steel shell (green), protecting them from corrosion.


uSacrificial anode (left) and powered anode.


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56