This page contains a Flash digital edition of a book.
Advertising: 01622 699116 Editorial: 01354 461430


Most cables designed for permanent installation within domestic, residential and commercial


buildings and other civil structures are now subject to the Construction Products Regulation (CPR), covered by EN50575. Since becoming a legal requirement in July 2017, it is important to understand how CPR affects installations and the choice of cables.


PR aims to ensure designers and installers are better aware of the contribution cables make to the spread of fire. Cables are a particular concern as they run between rooms and floors, above ceilings and are often made from flammable materials. The regulation includes seven classes, but only five will apply to cables. As well as testing, full traceability of raw materials, quality and production process have to be recorded and maintained. Class Fca is a basic vertical flame test that can be carried out at manufacturer level. FS Cables has invested in a test rig to EN60332-1-2 to enable a better understanding of how cables perform and where appropriate, classify to Class Fca. To meet Class Fca, a cable must burn more than a set amount, essentially burning ‘too much’ to meet Class Eca. For a cable to meet Class Eca, it must undergo the same vertical flame test but this must be carried out by an authorised test house. If the cable burns less than the set amount, it can be classified as Class Eca. Classes Dca, Cca and B2ca are also likely to apply to cables. All must go through a full scale fire test, conducted by a Notified Body. These tests measure the heat and smoke release of the cable. At Classes B2ca and Cca, flame spread is also measured and an annual factory audit by an


uA full scale fire test on cable.


INDUSTRY COMMENT BSEE


What does CPR mean for consultants and specifiers? C


authorised body is required. There are no tests for halogens or acid gases at this point – this involves tests known as S.A.D (smoke, acidity, droplets). It is unlikely for cables to meet Classes Aca and B1ca simply due to the materials they are made of. Pyro or MICC are the only products likely to. When specifying, it’s tempting to go for the highest class, but this won’t work as a large number of cables either won’t pass the tests through their design or are uneconomical to test to a higher level. Many data, control and signal cables will only meet Class Eca without redesign and potentially more significant, increased costs. Choose products that are appropriate for the application. Cable available on the European market before July 1st, 2017 can still be used, as can stock held in stores or vans.


When specifying cable, take care to assess the risk of fire within the building and the potential ease of evacuation.


Specifiers and designers should still look at the emissions of cables when burnt and in this case, specifying Low Smoke Halogen Free (LSHF) is just as critical. A cable may meet Class Eca in CPR terms but this gives no indication of its toxicity. Also be cautious of ‘LSF’ cables; this term is often used to


describe PVC-based products. Any product that contains PVC insulation, bedding or jackets can potentially be dangerous when burnt.


How to stay compliant


The cable itself is not required to be printed or embossed to show CPR compliance, although the regulation is very clear that the packaging must carry specific information, likely to be on the label. This will include the CE mark, DoP reference and unique product type.


A Declaration of Performance (DoP) should be available for any CPR- compliant cable. This document shows critical information, such as manufacturer’s name, product type


and class met. By law, manufacturers of CPR-compliant cables need to keep records of products and batches sold, together with DoP documentation, for up to 10 years after the date of sale. The obligation of the reseller (distributor) is to give the end user a method of obtaining the DoP either directly or from the manufacturer. All FSC-marked cables will carry a batch number to give full traceability about when and where the cable was made and also the materials and production processes used to manufacture that specific batch. FS Cables has a readily-available range of CPR-compliant products.


www.fscables.com/cpr


VISIT OUR WEBSITE: www.bsee.co.uk


BUILDING SERVICES & ENVIRONMENTAL ENGINEER NOVEMBER 2017 11


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56