BSEE
The way heang system design is approached can have a significant impact on the energysaving potenal of a building. This does not only concern the choice of heang equipment including setup but also looking at such details as room height and building occupancy. Making use of builtin boiler controls and ancillaries such as temperature sensors to feed informaon back to them oers an integrated approach to heang eciency. This way, comfort levels are maintained, which has a posive eect on the wellbeing and producvity of building occupants. Consequently, maximising the use of control technology has benefits beyond heang costs
BOILERS & HOT WATER
At the flick of a switch – using builtin controls and external sensors for efficient heating system design
By Trevor Struck, area sales manager at Hamworthy Heating
‘One size doesn’t fit all’ approach to heating areas
W
hen planning a heating system, you should consider what each part of a building is used for. On the one hand, kitchens are an example where heat is generated by appliances such as ovens, hobs but also – which seems
counterintuitive – fridges. Another so-called free contributor is solar radiation, especially where the sun shines through windows or large glass panels, causing space to heat up quickly. Where humans are present, so is heat radiation.
Additionally, lighting and IT equipment such as servers and computers also have an impact. This is why heat requirements in these areas are lower than in other parts of the building where no or little free contributions are present. On the other hand, corridors are only used intermittently and do not require constant heating, as they are only passed through to get to another part of the building. Accordingly, it is essential to divide a building into different heating zones to avoid underheating one or overheating other areas. Thereby, required energy is effectively minimised which reduces the costs to warm the building - heat is provided when it is needed, where it is needed, and at the right intensity.
How to track free contributions?
Internal space temperature sensors measure the air temperature and do not only monitor the performance of the heat generators and the various heating circuits but can also track heat generated by appliances, processes and people as outlined paragraph above. The sensors should be positioned in carefully selected locations away from direct sunlight or other factors to avoid affecting measurements, giving an inaccurate picture of the actual room temperature.
Building layout and design as influencing factors
uHigh ceilings such as in a church or cathedral increase the heat up me dramacally
When it comes to building layout, there is a variety of factors to take into account for correct and efficient boiler control setup. For one, how quickly a space responds to heat, the thermal inertia of the building, needs to be considered. An office with low ceilings is an example for a space with low thermal inertia. With less air present, it will heat up faster and reduces the required start time before occupants arrive. In places with large volumes of air, such as in a church, high thermal inertia will increase the needed heat up time dramatically. High ceilings go hand in hand with poor heat distribution, unless suitable equipment to solve this issue is installed. Accordingly, it is vital to calculate an adequate time to switch on the boilers in the morning. On the other hand, an early switch off before occupants leave can help to achieve
crucial energy savings. Modern controls will self-learn this when set up correctly, although fine tuning is still necessary and recommended throughout the first year of occupation. Another factor affecting heating properties is heat loss. It occurs on surfaces which make up the building envelope which separates a building from the outside (such as walls, floors, roof, windows etc.) but also from gaps in it where cold air can come through. These effects can be felt especially in the winter months with low temperature and winds. Therefore, monitoring the external temperature at any given time to estimate the heat loss from the building is necessary.
Multitasking as a standard
Modern boiler controls can ’multitask’. They can optimise the heat output of heat generators, heating circuits, and heating control. However, lack of knowledge means they are often not used to their full advantage.
Correct setup helps to improve efficiencies and extend the lifetime of the products, as it ensures even use across the installation. Given larger turndown ratios – the operational range of the boiler – increases with the number of boilers used, installing multiple boilers rather than one can reap significant energy-saving benefits. Heat requirements are matched by several boilers which operate in a more efficient mode together rather than only one providing all the heat at a higher, less efficient modulation. This is where built-in boiler controls are especially beneficial.
In multiple boiler arrangements, the boilers can be set to operate in different modes.
In unison control, the controller attempts to hold as many boiler modules firing at the same time to match the base load of the building. The aim of this setting is to have them all modulate to more efficient low fire together. In cascade control, the controller attempts to match the base load with as few boiler modules as possible. Each method has its own merits dependent on the hydraulic configuration local to the boilers. Another benefit of multiple boilers is the availability of a backup during service or breakdown. While one boiler is out of use, others can step in to cover the heat demand without interrupting the heat supply. Additionally, using multiple boilers ensures even use across the installation for a longer product life, avoiding over- and underuse of individual boilers.
Looking beyond the boiler
To make the best use of modern technology, the heating system should be looked at as a whole. Efficiencies can be improved by using advanced boiler controls, sensors, mapping out high/low use areas of a building, and considering heat up time. With the use of multiple boilers in combination with built-in controls, further energy savings can be achieved. This benefits not only carbon emissions and energy costs but can also extend the reliability and lifetime of a system.
14 BUILDING SERVICES & ENVIRONMENTAL ENGINEER JANUARY 2020 Read the latest at:
www.bsee.co.uk
uSome builtin boiler controls can control mulple boilers at once and help to ensure even use across the installaon
‘
Correct set up
helps to improve eciencies and extend the lifeme of products, as it ensures even use across the installaon
’
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42