THE SENSOR REQUIREMENTS OF DATA CENTRES


is heavily affected by turbulence in energy costs, so there is a very strong demand for energy efficiency. At the same time, governments around the world are looking to energy hungry industries for opportunities to reduce the use of fossil fuels and lower greenhouse gas emissions. Around 60 per cent of a data centre’s energy


D


requirements are driven by its IT infrastructure, so there are energy reduction opportunities in (usually new) equipment that is more energy efficient. However, there are good opportunities for energy efficiency in the other 40 per cent of energy demand; the majority of which comes from a data centre’s cooling and air-conditioning systems. Efficient temperature and humidity control is


important for the optimal functioning of IT infrastructure. In many modern facilities 99.999 per cent uptime is expected; representing annual downtime of just a few minutes. These extremely high levels of performance are necessary because of the importance and value of the data and processes being handled by the IT infrastructure. In common with all good process efficiency


measures, effective energy management relies on the availability of accurate, reliable, continuous monitoring data. So, for data centres, what must be measured? And where?


TEMPERATURE


Cooling and air conditioning is necessary to remove the heat generated by IT equipment; to avoid over- heating and prevent failures. It is therefore necessary to monitor temperature in the aisles and racks, as well as in all spaces, ducts in the ventilation system, cooling system pipes, and outdoors. Naturally, it is vital that the measurement locations are truly representative and that the network of sensors is able to detect any potential cold- or hot-spots. Larger data halls can be more challenging to monitor because they have a greater potential for spatial temperature variability, so it is important that there are sufficient numbers of temperature sensors to ensure that all servers are monitored. Some servers may be close to a cooling unit and others may be further away; some may be at the bottom of a rack, and others higher up, so there is potential for three-


68


By Anu Kätkä, global product manager, Vaisala Industrial Measurements


ata centre owners and managers are acutely aware of the need for better energy efficiency. With responsibility for around one per cent of global electricity consumption, the sector


dimensional variability. In addition to a sufficient number of sensors, it is also therefore important for air flow and cooling to be optimally distributed throughout the server room. Most data centres will need to monitor ‘delta T’ - which is commonly defined as the temperature difference between hot and cold aisles. However, in reality, the situation is more complex because there are actually four different delta Ts that need to be monitored if cooling operations are to be as efficient as possible. The most obvious delta T is the temperature


difference in air before and after it passes through the IT equipment. The second frequently measured delta T is the temperature difference across the cooling equipment. However, in reality, the temperature of the air leaving the coolers is rarely the same as the air arriving at the IT equipment. This is usually because of issues such as obstructions, vortices, pressure differentials, air pockets etc. that cause cold air and warm air to mix. Similarly, the temperature of the air leaving the IT equipment is frequently cooler by the time it enters the coolers. This is usually because cooled air mixes with the warmed air for a variety of reasons; all of which indicate inefficiency in air flow management. So, the four delta Ts are the temperature differences:


1. Before and after the IT equipment 2. Before and after the coolers


3. Between air leaving the coolers and air entering the IT equipment


4. Between air leaving the IT equipment and air entering the coolers By accurately monitoring these four delta Ts, data


centre managers can gain a better understanding of the factors affecting cooling inefficiency, which can then inform mitigation and improvement measures to fine tune data centre performance. In dry climates evaporative cooling is effective at dissipating heat. In cold climates direct cooling with dry, cold air can be used. In recent years, liquid cooling solutions have become popular because they are more


October 2022 Instrumentation Monthly


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85  |  Page 86