FEATURE TRANSFORMERS & SWITCHGEAR


LOW VOLTAGE SWITCHGEAR: MAKING THE RIGHT CHOICE


Low voltage switchgear forms a vital part of the link between generation, transmission or transformation equipment on one side, and the lighting, motors and information technology on the other, says Gary Parker, senior technical engineer, ECA


I


t is defined as a collection of components, including but not limited


to, circuit breakers, switches, off load isolators, on load isolators, disconnectors, fuses, enclosures etc. In essence, all the accessories required to protect a low voltage system. The main functions of switchgear are


electrical isolation, isolation of sections of an installation, and local or remote switching. Here, ECA will focus on the different types of protective devices and the main considerations when selecting and specifying low voltage switchgear.


SELECTING SWITCHGEAR There are many devices designed to interrupt power, from a source to a load, and they each have different functions and characteristics. Selecting the right device for the right application is vital. Miniature Circuit Breakers (MCBs) are


probably the most common form of protective device used in electrical installations. Their use and characteristics should be well known and familiar to most professionals. Moulded Case Circuit Breakers (MCCBs) or simply circuit breakers, are commonly used for sub-main distributing loads in switchgear. The variety of sizes available means they


can be used in many circumstances where other forms of devices would be unsuitable. Advances in the ‘intelligence’ of these devices is enabling building managers to remotely monitor loads and better manage energy use. Many MCCBs have a variety of adjustable settings that can assist in providing protective device selectivity throughout an installation.


22 OCTOBER 2019 | ELECTRICAL ENGINEERING


MCCBs are often found in installations


where the maximum prospective short circuit currents are potentially very large. Many manufacturers now produce MCCBs with capacities in excess of 100kA. Where the downstream protective device


is a fuse, many adjustable CBs will need to have an I2


t on/off function, also referred to


as an in/out. ‘On’ results in an inverse time delay characteristic that most closely resembles time/current characteristics of fuses. ‘Off’ results in a constant delay characteristic that coordinates best with thermal-magnetic and electronic trip circuit breakers. Air Circuit Breakers (ACBs) are often


used at the origin of larger installations, due to their rating and ability to withstand high levels of faults. One consideration when selecting ACBs


is the option of fixed or withdrawable type. Fixed ACBs are generally less expensive than the withdrawable variety, but can be more challenging to maintain and isolate safely. A withdrawable ACB will not require isolation of the upstream protective device as there is no need to access terminals or connections. Where protection is offered by an ACB,


this is usually incorporated in a separate protection module. These modules are usually plugged into the ACB and eliminate the need for external protection systems. Motor Protection Circuit Breakers


(MPCBs), as their name implies, are specifically designed to protect motors, compressors and other motive power loads. Like a typical MCCB, these devices offer additional protection against motor


overload and phase loss in balanced three-phase systems. Contactors are solenoid operated


switching devices, usually remotely operated, that are designed to undertake repeated cycles of operation. BS EN 60947-4-1:2010+A1:2012 (contactors and motor-starters - electromechanical contactors and motor starters) gives specific information about these devices.


SAFETY FIRST, COST SECOND When specifying low-voltage switchgear assemblies, particularly the forms of separation, ultimately the greater the degree of protection, the greater the cost. This can initially be seen as a barrier to selecting the more expensive options, but this should not be the case, as an appropriate selection can ensure that not only does the installation provide safe working situations for those working on/near it, but it can also reduce down-time when maintenance is required. As a rule of thumb, the higher the form


of separation, the larger and costlier the assembly. This will impact on the selection should space and budget be limited, but it should never override safety.


* Note: BS EN 61439 specifies the requirements for low-voltage switchgear and assemblies, while BS EN 60947 specifies the functional units within the assemblies.


This article is based on an extract from ECA’s Application Guide: Selection of LV Switchgear and Protective Devices. The full 49-page document is available to ECA Members and can be accessed at www.eca.co.uk/technical.


ECA eca.co.uk 


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60