backup are rarely permitted to operate routinely. Gas engines designed for continuous running can follow a dispatch signal within their permit limits. Operating in parallel with the network is a different proposition from running islanded. The Energy Networks Association’s G99 requirements govern generation connected to distribution networks, and larger transmission- connected sites must also meet the Grid Code. Export limitation schemes under G100 may make reduced imports simpler to deliver than export. The stability question also runs the other way.
ENTSO-E’s May report on data centres noted that uninterruptible power supplies can transfer a site off the grid in response to a minor disturbance. At hundreds of megawatts, that sudden loss of load is a system event in its own right. Fault ride-through settings, ramp rates and the way a site returns to grid supply need to be factored into the design brief. The same report found hyperscale operators are best placed to offer flexibility, while colocation sites are constrained because tenants control the IT load.
When does grid support make sense?
The commercial case is just as important as the engineering. Not every data centre will have spare capacity to offer, and not every network will be able to use it. Operators need to weigh potential revenue against fuel costs, maintenance, network constraints and permitted running hours, while ensuring sufficient capacity remains available for
the facility itself. The UK Government is also exploring voluntary flexibility arrangements for major electricity users, potentially creating further opportunities.
Britain still needs more electricity network capacity to support its growing digital infrastructure. Yet if developers are already investing in generation and storage to get their facilities operational, it makes sense to consider what those assets could offer the wider system. Whether that’s reducing imports during periods of high demand or exporting spare electricity, the necessary protection, controls and connection arrangements need to be considered early. It’s considerably easier to plan for those possibilities before the switchgear has been ordered.
www.rehlko.com
electricalengineeringmagazine.co.uk
ELECTRICAL ENGINEERING • NOVEMBER 2026 21
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36