• • • LIGHTING • • •


WAREHOUSE LIGHTING MEETING NEW STANDARDS


High bay or low bay?


BY ANTHONY MARTINDALE, SENIOR PRODUCT MANAGER, COLLINGWOOD LIGHTING


With the need to upgrade privately rented non domestics buildings over 1000m2 to an EPC rating of B or above by 2031, there is a lot of work to do. For industrial buildings, the most cost effective first step to save energy is to replace the lighting with modern LED high bay luminaires. With lighting accounting for between 50 to 80 per cent of the electricity cost, high bay LED fittings can reduce this by up to 80 per cent, giving a payback of less than 2 years.


A


Getting the lighting right Good lighting in these buildings also boosts productivity and ensures safety. It is crucial for picking goods, navigating spaces, and avoiding workplace accidents.


It’s best to start with an audit to identify what fittings you will need, and if there are areas that lack illumination or are too bright. You may choose to use the existing luminaires’ locations to save money, but don’t assume that this is the case. Modern LED fittings are more efficient than older metal halide ones so you can use fewer to save on installation costs and future electricity usage.


electricalengineeringmagazine.co.uk


ccording to a recent report from Savills 78 per cent of warehouses in the UK have an EPC of C or below.


The ceiling height will affect the light dispersion and the fitting’s output requirements (lumens). The higher the ceiling the more lumens you will need from the fitting, but the wider you can space them apart.


While there is some overlap you would typically use low bay fittings for ceiling heights of up to 7 metres and high bay fittings for anything higher. Exactly what fittings you choose will depend on what light levels you need and whether the space is an open area or has racking.


Open areas


Most open spaces will need high bay fittings with a wide beam angle of about 100° to provide uniform illuminance. Working warehouses are typically manned, so to meet BS EN 12464-1 you should provide 200 lux of lighting at floor level. How many lumens per fitting you need to achieve this will depend on the ceiling height, optics and the reflectance off the ceilings and walls. You will also need to consider the spacing between fittings and the beam angle. A good lighting manufacturer should be able to help you with this. For greater installation flexibility choose high bay fittings where you can switch the wattage to alter the lumen output.


Aisles For areas with racking, CIBSE recommends lighting levels of 100 lux at floor level and 150 lux for safe passage. But you must also think of the lighting on the vertical plain to aid accurate picking, here you will need 200 lux.


Choosing a fitting with different beam angles can help you achieve the right lighting levels according to the height of the ceiling and the width of the aisles. For general lighting, a symmetric beam which distributes the light evenly is ideal, but for aisles it is better to select an asymmetric beam that has a rectangular distribution of light.


Plan for change


It’s also worth planning for the future, with many warehouses combining different functions in the same area. A large space may contain both open areas and racking, and these may change to reflect new storage needs.


Changing the fitting to meet new needs is difficult when they are more than 8 metres above the floor. Fortunately, there is an answer with adaptable high bay lighting, taking our Tri Bay range as an example, you can switch the beam angle from 100° for open areas to 30° x 90° for lighting long rows of racking.


Lighting control Remember that warehouse lighting refurbishments need to maximise energy savings and most will have skylights providing free natural light. Specifying daylight harvesting and motion sensors ensure that you only use artificial lighting when you need it to save more energy.


Modern warehouses are a vital part of our life. There is a hard deadline for them to meet tougher energy requirements by 2031. A lighting refurbishment is the obvious place to start and it will quickly pay for itself.


www.collingwoodlighting.com ELECTRICAL ENGINEERING • NOVEMBER 2026 13


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36