• • • POWER • • •


DATA CENTRE BRIDGE POWER SHOULD BE


DESIGNED FOR THE DAY THE GRID ARRIVES


use the Covenant to think about how these assets might contribute to the wider electricity system throughout their operating lives.


BY ALEX MARSHALL,


GROUP BUSINESS DEVELOPMENT AND MARKETING DIRECTOR, CLARKE ENERGY, A REHLKO COMPANY


he Government’s new Data Centre Covenant, published alongside October’s Budget, has shone a fresh spotlight on the grid and the challenge of supplying the power for the UK’s data centre ambitions.


T


The plans propose a tightly controlled framework for strategic projects to use temporary on-site generation while they wait for a connection. The reason is because demand for connections is already extraordinary. Ofgem’s July consultation reported that contracted demand in the connections queue rose from 41GW in November 2024 to 125GW in June 2025, with at least 80GW associated with data centre proposals. Of course, not all of those project plans will be realised, but even a fraction of that development would require considerable investment in generation, networks and electrical infrastructure. The data centre industry clearly requires significant power to fuel the digital economy, but as developers consider installing their own generation and storage, there is an opportunity to


Different timescales,


different tools Britain’s electricity system needs flexibility over very different timescales, and balancing short-term and long-term needs is the main challenge to think about. Sometimes, a frequency deviation may demand a response within seconds. At other times, more planning is required for the times when mother nature sets the rules.


The Germans have a word, Dunkelflaute, which means a cold, still spell when wind and solar output are both low. As we enter the time of year when the sun sets while we’re still in the office, Dunkelflaute can last days. As renewable generation becomes a larger part of the electricity mix, engineers must therefore plan for these prolonged conditions alongside the moment-by- moment adjustments needed to keep the system balanced. Battery energy storage systems (BESS) are particularly effective at responding quickly when needed to manage short fluctuations. Their duration, however, depends on the energy stored. Meanwhile dispatchable generation can sustain output for days, subject of course to fuel, maintenance and emissions limits. NESO’s Winter


20 ELECTRICAL ENGINEERING • NOVEMBER 2026


Outlook, published in October, expects sufficient supply this winter from a mix that includes gas, wind and batteries. Maintaining reliable supplies as demand grows will require technologies with different capabilities working together. A connected data centre equipped with on-site generation and BESS could provide some of that flexibility. A site can reduce imports from the grid during periods of network stress by running its own plant, but where it has surplus capacity, it can also export back to the wider system. Both approaches help, but their technical requirements and commercial arrangements differ considerably.


Designing for both roles Any contribution has to start with the site’s own requirements. A battery reserved to maintain continuity during a power interruption cannot simultaneously be counted on to provide grid services. Similarly, generating capacity required to maintain redundancy cannot automatically be treated as available for export. Switchgear, protection and energy-management controls have to manage these competing roles. Another thing to think through is the type of generation. Environmental permitting treats standby plants that run only for testing and emergencies differently from plants that run to provide balancing services. Diesel sets sized for


electricalengineeringmagazine.co.uk


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36