• • • ANALYSIS • • •
Putting solar installations to the test
Electrical inspection and testing of solar PV installations is a fundamental requirement to ensure system safety and performance, said Darren Bakewell, applications engineer at Seaward Solar
T
he safe operation of solar PV installations under both normal and fault conditions is an essential consideration at the system design
stage to ensure that proper energy outputs and safety levels are achieved. And once in operation, it is important to ensure
that the long-term performance of the system is not compromised by sub-standard installation or poor maintenance. In this respect, there are some key solar PV
system features that rely on adequate and appropriate electrical testing and inspection being undertaken on a regular basis.
Compliance with IEC 62446 IEC 62446 recommends that periodic verification of an existing installation shall be performed. The standard defines the minimum requirements for system documentation, commissioning tests and inspection for PV systems. As such, this standard not only specifies the
minimum electrical testing and inspection requirements but equally importantly how the inspection and test results are documented and supplied to the consumer after installation. Where appropriate, the results and
recommendations of previous periodic verifications shall be taken into account. A periodic verification report shall be provided and include a list of any faults and recommendations for repairs or improvements (such as upgrading a system to meet current standards).
Effective grounding As with all electrical equipment, solar panels and their racking systems must be grounded to mitigate potential electric shocks and fire hazards. If the grounding system degrades over time, anyone who comes into contact with a metal piece of the system may receive a shock. While the likelihood of shock is
low, should one occur, the chance of substantial injury is great, because of the high voltage arrays, and the added danger of falling from roof mounted systems.
Ground faults PV systems, in particular large-scale systems, have many metres of cabling, much of which is buried underground. Poor levels of insulation will allow energy generated by the PV system to leak to earth. This can be particularly problematic during damp or wet
12 ELECTRICAL ENGINEERING • NOVEMBER 2022
conditions where the insulation monitoring or residual current monitoring function within an inverter prevents the inverter from starting up which in turn can significantly reduce the operational efficiency of the PV installation.
Environmental degradation PV systems by their very nature are exposed to the elements. Damage or corrosion to cabling and connectors caused by moisture ingress can result in degradation in performance or increased risk of fire. Regular electrical testing will enable system performance to be monitored and any necessary repairs or remedial actions to be taken
Surface contamination
and physical damage PV modules can become dirty or contaminated over time and this can reduce the operational efficiency and system performance. Similarly, exposure to the elements can result in physical damage to the component parts of a PV installation. Objects dropped by birds can result in physical
damage to PV modules which may result in reduced output performance. Periodic electrical testing as part of regular maintenance will enable any problems to be identified and diagnosed.
Damage to wiring The most obvious example of bad wiring is when wires hang below the panels and touch the roof or underlying vegetation. Eventually the wire coating will wear or be damaged by rodent attach and potentially expose the copper wires, presenting a shock hazard.
Any deterioration of cable connections and
wiring can be identified by applying regular electrical testing to identify potential faults.
Verification of system
performance The installation of solar PV systems is only undertaken after careful consideration of the costs involved and the potential return on investment provided by lower energy bills and FIT payments. As a result, the verification of system
performance and energy output from the panels is particularly important. In many cases simple electrical faults or wiring failures can cause a serious inefficiency in the ability of the panel to produce power. Although proper metering will give an indication
of system performance, periodic electrical testing is vital to verify ongoing functional performance over extended periods.
Warranty fulfilment Periodic electrical testing of solar PV systems to identify and confirm continued safe operation and maximum energy output performance can be required as part of product warranties and PV system component guarantees.
Avoiding fire risks As the number of rooftop solar installation systems have grown over the years, so have the number of reported incidents of fires. Household fires started by electrical faults in rooftop solar PV systems have been reported in the UK, Australia, the USA and France – among others. The periodic testing of the electrical cabling and components associated with solar PV systems will ensure the safe operation of the system and reduce the potential fire risk associated with any electrical faults.
Customer documentation All solar PV installations require the provision of various documentation and forms to the customer. System documentation usually includes system data, installer details, electrical diagrams, operation and maintenance instructions and other information that may be required by certain standards or regulatory bodies. Copies of all test and commissioning data should also be provided and as a minimum this should include the results from the electrical safety and verification tests undertaken as part of the system installation
electricalengineeringmagazine.co.uk
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48