• • • SURGE & CIRCUIT PROTECTION • • •


protection critical for it to last its designated lifespan.Lightning is an electrical discharge in the atmosphere. When lightning strikes, fires are prone to happen due to the release of energy. Nimbus (rain) clouds, have a concentration of electrical charge, and their accumulation creates an ionization of air. The ionization of air that is between the ground and the nimbus clouds creates a discharge from the clouds to the ground. Nimbus clouds cause the biggest surges because they are what generate lightning. Indirect lightning strikes are destructive.


Surge protection devices for solar applications L


ightning’s perfect storm for destruction is on the solar field. Solar panels’ large—and often exposed and isolated—location make surge


system is located on an industrial site, the business operations and equipment are also at jeopardy. Inverters are expensive, but for industrial applications, an even more expensive failure is the cost of downtime and data loss. When lightning strikes a solar PV system, it


Anecdotal observations about lightning activity is usually a poor indicator of the level of lightning- induced overvoltages in photovoltaic (PV) arrays. Indirect lightning strikes can easily damage the sensitive components within PV equipment, which often has a high cost to repair or replace the damaged components, and affects the PV system’s reliability. Photovoltaic systems are exposed in large open


spaces, typically in fields or on the tops of buildings. Charged rain clouds that accumulate over such open fields have the propensity to release the charge in the form of lightning. When this happens, a voltage surge is likely to occur. The more expansive the field is, the more likely destruction is to occur. Electronic equipment can easily be damaged to


the point of catastrophic failure by surges. If a surge occurs when any personnel are present, it will jeopardize their safety as well. Indirect lightning strikes can be fatal if the person is within 60 feet from the point of the lightning strike. When a PV


electricalengineeringmagazine.co.uk


causes an induced transient current and voltage within the solar PV system wire loops. These transient currents and voltages will appear at the equipment terminals and likely cause insulation and dielectric failures within the solar PV electrical and electronics components such as the PV panels, the inverter, control and communications equipment, as well as devices in the building installation. The combiner box, the inverter, and the MPPT (maximum power point tracker) device have the highest points of failure. To prevent high energy from passing through


electronics and causing high voltage damage to the PV system, voltage surges must have a path to ground. To do this, all conductive surfaces should be directly grounded and all wiring that enters and exits the system (such as Ethernet cables and ac mains) be coupled to ground through a surge protection device (SPD). An SPD is needed for each group of strings


within the combiner box, the recombiner box, as well as the dc disconnect. Photovoltaic PV systems have unique


characteristics, which therefore require the use of SPDs that are specifically designed for PV systems. PV systems have high dc system voltages up to 1500 volts. Their maximum power point operates at only a few percentiles below the system’s short circuit current. To determine the proper SPD module for the PV system and its installation, you must know:


• • • • •





the lightning round flash density; the system’s operating temperature; the system’s voltage;


the system’s short circuit current rating;


the level of waveform that is to be protected against (indirect or direct lightning); and


the nominal discharge current. The SPD requirements for an installation that is


protected by an external lightning protection system (LPS) depend on the selected class of the LPS and whether the separation distance between the LPS and the PV installation is isolated or non- isolated. IEC 62305-3 details the separation distance requirements for an external LPS. To have a protective effect, an SPD’s voltage


protection level (Up) should be 20 % lower than the dielectric strength of the system’s terminal equipment. It is important to use an SPD with a short circuit


withstand current greater than the short circuit current of the solar array string that the SPD is connected to. The SPD that is provided on the dc output must have a dc MCOV equal to or greater than the maximum photovoltaic system voltage of the panel. When lightning strikes at point A (see Figure 1),


the solar PV panel and the inverter are likely to be damaged. Only the inverter will be damaged if the lightning strikes at point B. However, the inverter is typically the most expensive component within a PV system, which is why it is essential to properly select and install the correct SPD on both the ac and dc lines. The closer the strike is to the inverter, the more damaged the inverter will be.


LITTELFUSE littelfuse.com


ELECTRICAL ENGINEERING • NOVEMBER 2020 33


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52