Renewable Energy
The advantage of speed for damper drive applications
For combustion air and flue gas applications, some critical services are very dependent on rapid speed to ensure equipment life, operator safety and peak plant performance. Rand Underwood reports.
A
t the Florida Power & Light 3-Unit Manatee Station, a 2,735MW generating plant in Parrish, Florida, Rotork Type K damper drives have provided a solution to a critical application demanding quick
damper operation. In the case of balanced-draft power generation
boilers, low pressure conditions inside the combustion chamber can lead to some very serious equipment failures.
Te ID Fans on a combustion boiler play a critical role in maintaining that reliable boiler pressure. Te ID Fan Inlet Damper Controls that regulate fan induced pressure and airflow need to be vigilant ‘soldiers at the ready’ to help keep these pressure fluctuations in check. Te ID Fan Damper Inlet Drives required for
Florida Power & Light Manatee Station Units1 & 2 require full 90 degree drive and damper movement at full torque load in three seconds or less to safeguard the operation of the boilers. Te existing drives were in excess of 30
years old. In addition, they were not HART compatible with the plant’s new DCS system and the manual overrides were unreliable on the aging damper drives. Type K offered a drop-in-place retrofit
drive matching the existing damper drive footprint that featured smart positioner technology and integrated air volume boosters to obtain the rotation speed required. Type K also completed factory acceptance testing on the drives and obtained the test cycle times as recorded by the smart positioner. Te results of the testing were video
recorded and documented for Florida Power & Light to review prior to shipment. Te on-site performance testing for
Fig. 1. The Type K damper drive ‘drop-in-place’ replacement matches the footprint of the old equipment. Note that the handwheel has been re-engineered in the vertical position to facilitate access to the hinged man-way door behind the unit, which provides access to the ID fan for servicing.
Boiler pressure transients can cause combustion issues that lead to irregular heating in the steam tubes. In extreme conditions, excess negative boiler pressure can collapse boiler walls and buck stays, leading to additional catastrophic failures such as ruined boiler tubes and refractory or even wholesale structural damage.
Te nature of these events often equate to long term
unit shutdown, lost kilowatt production, and expensive emergency site construction repairs. Power generation boilers need a somewhat consistent internal operating pressure environment for efficient and manageable combustion.
54
www.engineerlive.com For more information ✔ at
www.engineerlive.com/ipe
Rand Underwood is General Manger of K-TORK International Inc, part of the Rotork Group., Bath, England, UK.
www.rotork.com
damper drive speed was conducted at the power plant early on a Sunday morning at about 2:00AM. Tis was a full load / installed equipment proof-test scheduled typically toward the end of a planned outage. Tis acceptance test is critical to build confidence in the plant unit trip and boiler shutdown process.
Te Type K Drives performed as quickly and as smoothly as factory testing had indicated. At full boiler pressure and damper load, the drives rapidly failed to the fully closed position as required. Passing this test is primary to outage completion and full sign-off for boiler readiness to generate electricity. ●
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48 |
Page 49 |
Page 50 |
Page 51 |
Page 52 |
Page 53 |
Page 54 |
Page 55 |
Page 56 |
Page 57 |
Page 58 |
Page 59 |
Page 60 |
Page 61 |
Page 62 |
Page 63 |
Page 64 |
Page 65 |
Page 66 |
Page 67 |
Page 68