DATA CENTRES FANS C


ooling resilience cannot begin at the point of failure; it must begin earlier, by identifying small changes before they develop into a wider operational issue.


Traditional data centres often benefi ted from a degree of thermal buff er. Lower rack densities and large volumes of conditioned air could provide teams with more time to respond when cooling performance began to decline. High-density AI environments are diff erent. Greater heat loads mean temperatures can rise more quickly if cooling capacity is reduced. A minor performance loss that once may have developed gradually can now put equipment, uptime, and service-level commitments at risk much sooner. This changes the role of refrigerant leak detection. Rather


than treating detection solely as a compliance or safety requirement, design and engineering teams increasingly need to consider it as part of the facility’s wider cooling- resilience strategy.


Cooling disruption Refrigerant leaks are not always sudden or immediately visible. A small leak can develop gradually at a joint, valve, seal or other component, allowing the system’s refrigerant charge to decline over time. Initially, the cooling system may compensate. Compressors may run longer, controls may adjust, and temperature set points may remain the same. From an operational perspective, the system can appear to function normally even as its performance begins to change. As refrigerant levels continue to fall, cooling equipment may work harder to maintain the required output. This can contribute to increased energy use, place additional strain on system components and gradually reduce the cooling capacity available to the facility. In a high-density environment, continued refrigerant loss may eventually lead to a low-pressure trip or an inability to meet the thermal load. By then, the window for planned intervention may have narrowed considerably.


The challenge is that detection systems intended primarily to identify higher refrigerant concentrations may not alert teams during the earliest stages of a leak. A critical alarm can confi rm that action is required, but it may not provide the earliest opportunity to respond.


Early detection should begin at the design stage Cooling resilience is stronger when teams consider refrigerant detection during system design rather than adding it late in the project. Design teams can identify likely leak points, plan suitable sampling locations and determine how detection information will connect with building- management or facility-monitoring systems. Aspirated sampling pipework can also be incorporated while plant layouts, service routes and access requirements are still being developed.


This early consideration is especially important in large or complex cooling installations, where multiple pieces of equipment may need monitoring across separate plant areas. Sampling point locations can aff ect how quickly a developing leak is detected and how easily teams can identify its likely source.


During commissioning, high-sensitivity detection can


provide another layer of visibility. It can help engineering teams identify low-level refrigerant presence, installation issues, or emerging leaks before handing over the cooling infrastructure to the operator.


Once the facility is live, the same system can support a


more proactive maintenance strategy by showing where refrigerant is being detected and how readings are changing over time. This gives teams an opportunity to investigate while cooling equipment is still operating, rather than waiting for a fault, pressure trip or loss of capacity.


Aspirated refrigerant detection Aspirated refrigerant detection continuously draws air from multiple sampling locations back to a central sensor for analysis. This lets one system monitor several plant areas or potential leak points while still providing zone- specifi c information. Sampling points can be positioned close to chillers, compressors, valves and other areas where refrigerant leaks may develop. One example is the Bacharach® Multi-Zone gas monitor, which uses infrared sensing technology to detect supported refrigerants at concentrations as low as 1 ppm. A single monitor can sequentially sample up to 16 zones, giving design, commissioning and maintenance teams greater visibility across complex cooling infrastructure. This high-sensitivity approach can help identify low-level


refrigerant presence before it develops into a more signifi cant loss of charge. When detection information is connected to wider monitoring and alerting systems, teams can also review readings remotely, examine trends and prioritise investigation according to the location and development of an event. The value is not simply in generating another alarm. It lies in providing actionable information earlier in a leak’s progression.


Cooling resilience starts before failure As computing densities rise, data centres have less tolerance for unnoticed cooling degradation. A critical alarm may indicate that cooling performance is already at risk. Early leak detection lets you act sooner, while the system is still operating and before a low-level issue becomes a wider cooling disruption. By integrating high-sensitivity refrigerant detection into design, commissioning and maintenance strategies, data centre teams can gain better visibility of emerging risk and take a more proactive approach to protecting cooling performance and uptime.


"Aspirated refrigerant detection continuously draws air


from multiple sampling locations back to a central sensor for analysis. This lets one system monitor


several plant areas or potential leak points while still providing zone-specifi c information. Sampling


points can be positioned close to chillers,


compressors, valves and other areas where


refrigerant leaks may develop."


Download the ACR News app today 18-19 acrdcmsa.indd 19


www.acr-news.com • November 2026 19 26/10/2026 14:17


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36