FEATURE TEST & MEASUREMENT Lock out and safe isolation


Every electrician with experience working on a busy site knows how it feels to take responsibility for the other tradesmen around them. When dealing with electricity, there is no room for calculated risks and educated guesses. The only way you can ensure the safety of yourself and your colleagues is by adopting an adequate safe isolation procedure


about to work on is in fact dead. The recommended method for doing this is by using a test lamp or a two pole tester (as recommended in HSE Guidance Note 38). The test lamp or voltage detector should be proved to be working on a known live source or a proprietary proving unit. All line, neutral, and protective conductors should be tested to prove they are dead. Di-log’s latest range of safety


F


or electrical systems where the supply has been cut off to allow dead


working, Regulation 13 of the Electricity at Work Regulations 1989 establishes a clear requirement to ensure that conductors and equipment may not be inadvertently energised. In other words, safe isolation. In practise, this means not only cutting off the supply, but also ensuring the method of disconnection is secured in the ‘off’ position.


SAFE ISOLATION PROCEDURES Isolation of equipment or circuits using the main switch or distribution board switch disconnector, is the preferred method. The method of isolation should be locked off using a unique key, retained by the person carrying out the work, and a caution notice posted at the point of isolation. Where more than one operative is working on a circuit, a multi-lock hasp can be used to prevent operation of the main isolator, until such time as all persons working on the installation have completed their work and removed their padlocks from the hasp. The practice of placing insulating tape over a circuit breaker is not an acceptable means of securing the device in the ‘off’ position.


PROVING DEAD ISOLATED EQUIPMENT OR CIRCUITS Following isolation of equipment or circuits, and before starting work, it should be proved that the area you are


28 MARCH 2017 | ELECTRICAL ENGINEERING


equipment for working on LV electrical equipment includes an array of lockout kits, ranging from the simple single MCB Personal Lockout Kit, for isolation of individual circuits, through to the industrial Expert Lockout Kit with mostly fully insulated lockout devices for virtually all individual and main sources of energisation. The Di-log range of lockout kits are


designed with safety, versatility and affordability in mind. With the entry level DLLOC1 Personal Lockout Kit, you get a 38mm steel padlock, a universal MCB lock, a standard ‘pins-out’ MCB lock and warning tag. The higher the level of kit, the more features are included. By adding items, such as multiple isolation lockout hasps, the kits enable multiple persons to work on the same circuit, with the ability to hold up to six lockout padlocks. The DLLOC3 Professional and DLLOC4 Expert kits provide more scope to safely isolate a broader range of MCB’s and main switches. Items such as the larger universal MCB lockout device, large main switch lockout device, and fully insulated padlock and hasp, ensure all industrial applications are covered.


ISOPK1 AND ISOPK2 To fully conform to the ‘Safe Isolation Procedure’, and in addition to the above, once the circuit or main source of energy has been isolated, the conductors must be proved to be dead at the point of work before they are touched and, where necessary, caution notices should be applied at the point(s) of isolation. With this in mind, Di-log has combined its lockout kits with its award winning 2- Pole Combivolt Voltage Indicators and its PU260 690V 2-Pole Voltage Proving Unit, to create the all new ISOPK1 CombiVolt 1 Safe Isolation Kit c/w DLLOC1, and ISOPK2 CombiVolt 2 Safe Isolation Kit c/w DLLOC2.


Electricians who regularly work on installations that have been energised, should be equipped with devices for proving that conductors are dead


The CombiVolt Voltage and Continuity Indicators are packed with features, such as single pole voltage indication (even when the batteries are depleted), phase rotation and non-trip phase to PE indication. They also fully conform to all standards, including the vital BS EN 61243-3-2015.


The PU260 690V proving features LED


indication if your 2-pole tester draws excessive current above 3.5mA, thus not conforming to standards such a ‘Protection against Electric Shock’.


Di-Log www.dilog.co.uk





Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64