general medical needs and electricity to supplement the main grid supply and power the plant room.


“CHP electricity doesn’t suffer


transmission losses


resulting from moving power over large distances.”


Initially, when integrated with the BMS, the CHP unit did not run as expected. The running temperature for the heating system was set too high and the central heating pumps were operating in excess of the design required flow rate. As a result, the CHP unit would only run for a few minutes first thing in the morning and then stand idle for the rest of the day, significantly reducing the efficiency of the system.


The hospital uses radiant panels to distribute heat to the occupied spaces. Because of the excessive water velocity, they were struggling to deliver the required heat. As a result, the thermostatic controls were continually demanding more heat from the boilers. The R-Gen SenerTec Dachs is designed to provide pre-heated feed water to a 750-litre buffer vessel, which stores the heat until it is required. However, the excess water velocity was allowing the heat from the boilers to enter the buffer vessel, affecting the heat distribution from the CHP unit.


When one of our technical sales managers visited the hospital, he quickly realised that the CHP unit had been running for only a fraction of the time possible. By simply tweaking the boiler temperatures down by one or two degrees, he was able to get the CHP running as intended. The hospital’s maintenance engineer also reset the system pumps reducing the velocity in the system ensuring even distribution throughout the heating system.


The unit is now running almost continuously, meaning the hospital is benefitting from significant energy savings – the hospital’s energy bill has been reduced by around 30%.


CHP is a well-established, reliable technology with numerous successful installations throughout the UK, and across the world. However, if CHP is to deliver cost and carbon savings, the importance of correct design, commissioning, monitoring and maintenance must be fully understood.


www.remeha.co.uk twitter.com/TomorrowsEM MONITORING & METERING | 23


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38