Letters to the editor


Sam Dannaway, I read your article on AFFF for Aircraft Hangars (Plumbing Engineer, May – July) with more than a little interest since I happen to be an ex-USAF aircraft mechanic. Regarding VSR-type water flow switches, I can tell you


from 40 years’ experience that the pneumatic retards on these puppies usually start out pretty inaccurate out of the box, and only get worse over time. When it’s vital to not flow water unless there is an open head, the best way to handle wet pipe systems is with what used to be called a Gamewell Wet Kit Sprinkler Watchman. The kit super- vised both street and system sides of the check valve and maintained between 25 and 45 psi differential over street pressure on the system side of the alarm check. The main part of the system was an electric-motor dri-


ven Oberdorfer gear pump, which was controlled by a dif- ferential pressure switch. The kit contained other low pressure switches; one for Supervisory and one for Alarm. These switches, along with a pressure operated flow alarm switch, could be connected to fire alarm panels in a vari- ety of ways to meet site-specific needs. The kit part num- ber was M2700-15. The kit was discontinued by Gamewell because of the


cost difference between the kits and vane-type flow switches. Of course, most engineers and customers opting


Classifieds


Est’d HVAC/Plumbing Co. So. OR/No. CA.


100 yr old co with great rep. 2010 sales: $2.4M. 2011 on track to equal 2010 Owner retiring. 503-620-1800


tylerp@pipergroupinternational.com


Contact Sadie


Bechtold at 847.564.1127 to place a classified


ad today in


Plumbing Engineer!


for vane switches probably failed to fully understand the utility and value of the kit. There was a stripped down ver- sion (minus the alarm and supervisory switches) called an Excess Pressure Pump (“jockey pump” in trade lingo). The part number for that was 26615-7. I much preferred the kit because it gave you vital infor-


mation about what you had for water right at the alarm check and a means to summon a response if the street pressure dropped too low. If you, or someone in your position, were to approach Gamewell with the idea of starting up production on the


The only problem I see with using the kit is that if a sprinkler pipe was broken or


minimize (by location) the time delay between a flow and a system dump, because you can adjust the differential pressure switch based on a site record of high and low supply pressures over some period of time.


kits again, or even doing a special, one-time batch run, they might be willing to listen. The only problem I see with using the kit is that if a sprinkler pipe was broken or developed a serious leak, you’d still dump the foam, but it’s an unbeatable way to minimize (by location) the time delay between a flow and a system dump, because you can adjust the differential pressure switch based on a site record of high and low supply pressures over some peri- od of time. I’m pretty sure Oberdorfer still makes the pump. I have


a parts list for the kit, if you’d like to take a shot at fabri- cating one yourself. For most commercial applications, a VSR is OK


because the worst thing that you can do is inadvertently empty a building and call the fire department. Cleaning up 30 – 50' of AFFF is a whole other animal, which sudden- ly helps the cost differential make a lot of sense.


Cheers, Continued on page 74 PLUMB-TECH DESIGN & CONSULTING SERVICES, LLC


Plumbing, Piping, Fire Protection and HVAC System Design; foren- sic investigations for mechanical system failures; litigation support; code and standard consulting; technical writing and training semi- nars; and CAD services. 3525 N. Dixie Hwy., Monroe, MI 48162 Phone: (734) 755-1908


E-mail: ron@plumb-techllc.com Website: plumb-techllc.com


Page 72/Plumbing Engineer October 2011


developed a serious leak, you’d still dump the foam, but it’s an unbeatable way to


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76