PHAM NEWS | NOVEMBER 2024 Water& System Treatment 39 T
he new DosaFil DR solid products were specifi ed for a standard, 50-year old four bedroom
detached home on the outskirts of Liverpool. The heating system had not been treated before and no magnetic fi lter had been installed. It was a vented system with a hot water cylinder and had ten radiators, two of which were towel radiators. The heat source in the home
was a Baxi system boiler with an aluminium heat exchanger. Pipework for the system was a mix of copper and plastic. There was a UPS 15-50 system circulator fi tted to the system with an approximate fl ow rate of 10.1 litres/min. An independent local installer, Dave Jones from the fi rm Oil Gas Safe Ltd, was asked to undertake work in the property.
First steps On day one of the installation a fi lter was installed – a DosaFil B2 fi lter with 22mm compression connections installed on the return to the boiler. The system was bled and refi lled with fresh water via the F&E tank in the loft, before the boiler was set to run with all radiator TRVs fully open. The circulating water temperature was measured at the fi lter at 60°C. The water was left circulating
for 30 minutes and then a sample was taken from a dining room radiator and sent for laboratory analysis. An inspection of the bar magnet in the recently fi tted fi lter showed that there was already signifi cant magnetic particle capture. The system was then dosed with
three DR1 solid inhibitor capsules and one DR2 solid online cleaner capsule and these were added to the empty fi lter. The fi lter was topped up with system water and the custom manufactured commissioning cap fi tted before the fl ow was restored with the boiler producing heat. Some 25 minutes later, the
fi lter was opened and inspected,
Case study demonstrates the benefi ts of solid solutions
The recently launched DosaFil range of solid water treatment products are designed for use in commercial heating systems, but how well does it perform in a residential property? A recent application in a Liverpool home off ered an opportunity to test their application and monitor the results.
The DosaFil B2 fi lter was installed on the boiler return before the system was dosed with DR1 solid inhibitor and DR2 online cleaner capsules
showing that the capsules had fully dissolved and there was no residue evident in the fi lter. The inner fi lter insert and magnetic cap were refi tted and the system was again restarted with heat and circulation, this time running for 24 hours. A sample of the circulating
water was again taken from the dining room radiator, photographed and then sent for laboratory analysis.
Early results Day two began after 24 hours of constant circulation of the system, with the fi lter stripped for inspection and cleaning. Magnetite had collected on the fi lter’s magnet insert and there was light fouling on the fi lter element. A further sample was
taken from the dining room radiator and photographed. There was signifi cant visual improvement compared to the previous sample. This was again sent for laboratory analysis. Biocide dosing was undertaken
on the third day. A DR4 solid biocide capsule was added to the fi lter with the fi lter cartridge insert in place. Water was circulated with the boiler switched off initially and then switched on. The temperature of the water rose to 58.8°C. After 15 minutes the capsule had completely dissolved and the fi lter was reassembled with the magnet cap and the system was put back into circulation again. On day fi ve a sample was again
taken from the same dining room radiator, the fi lter was checked and cleaned and a sample taken from the system and again sent for laboratory analysis.
Laboratory tests The full chemical analysis results from the four samples sent to the laboratory provided some impressive results. The pH stabilised rapidly post-chemical dosing, while Molybdate reserves (the inhibitor) increased following dosing and then stabilised as all parts of the system achieved fl ow and the inhibitory fi lm was laid down within the system. Suspended solids increased
The DosaFil range of water treatment products
A system water sample taken before the application of the DosaFil treatment and a fi nal sample (after the addition of biocide)
after the addition of DR1 and DR2, as the cleaner mobilised the fouling present in the system. However, fi ltration rapidly brought the suspended solids levels down through eff ective magnetic and non-magnetic fi ltration. Aluminium levels increased
slightly following the addition of the DR1 and DR2, but the levels reduced quickly with eff ective fi ltration and treatment. Similarly, iron and copper levels increased but then reduced as suspended iron was removed by fi ltration. So to summarise – a full
dose of DR1 solid inhibitor x 3 capsules, and DR2 solid online cleaner x 1 capsule can be dosed to a gas boiler system in less than 30 minutes with water circulating at 60°C. Just 24 hours of continuous fi ltration and DR1 and DR2 treatment signifi cantly improved the circulating water quality. Water quality continued to improve with normal system operation as the online cleaning continued. Importantly, no system fl ushing was required to obtain an improvement in water quality – the radiator TRVs were simply opened fully and air bled. The solid water treatment
products performed exceptionally well and the whole process was undertaken without the need for power fl ushing and without any fl ushing to drain and refi ll – a huge reduction in the
use of water for the process over what many consider the standard method of treating a heating system. Using the DR treatment products with an eff ective fi lter proved to be eff ective for treating and cleaning a residential heating system and off ers several benefi ts over the standard cleaning methods using liquid chemical products.
Clear to see “I am impressed with the concept of the fi lter and solid chemicals as a package,” says Dave Jones from local installation business Oil Gas Safe UK. “It’s a fi rst for our team – but must admit the results speak for themselves. It’s clear to see that this package has made a signifi cant diff erence and has proved eff ective for treating and cleaning a residential heating system.” DosaFil Residential
Technologies MD Steve Crick adds: “We’re confi dent that this case study highlights the effi cacy of using the DR system to return a heating system to its most effi cient state and that this should be something that makes contractors and organisations such as social housing providers sit up and take notice that there is a more effi cient and sustainable way to achieve clean heating systems in homes, with the minimum of disruption to the resident.” ◼
phamnews.co.uk/1124/61
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48