The M9102 and M9104 Series Actuators are direct- mount, non-spring return electric actuators that operate on AC 24 V power. These synchronous motor-driven actuators provide floating control (AGA), floating control with automatic shutoff (IGA), and proportional control with selectable 0-10 or 2-10 VDC (GGA). The -2S models are equipped with plenum cables, and the -3S models are equipped with terminal blocks.
5 M9102 and
M9104 Series 18-35 in-lb
Year
Manufacturer Warranty
item M9102-AGA-2S
M9102-AGA-3S M9104-AGA-2S
M9104-AGA-3S
control type running torque travel time Floating
Floating Floating
Floating electrical connections
18 lb·in (2 N·m) 30 Seconds at 60 Hz 48 in. (1.2 m) UL 444 Type CMP Plenum Rated cable with 19 AWG (0.75 mm2) conductors and .25 in. (6 mm) ferrule ends
35 lb·in (4 N·m) 60 Seconds at 60 Hz 48 in. (1.2 m) UL 444 Type CMP Plenum Rated cable with 19 AWG (0.75 mm2) conductors and .25 in. (6 mm) ferrule ends
M9104-IGA-2S Floating or On/Off 35 lb·in (4 N·m) 60 Seconds at 60 Hz 48 in. (1.2 m) UL 444 Type CMP Plenum Rated cable with 19 AWG (0.75 mm2) conductors and .25 in. (6 mm) ferrule ends
M9104-IGA-3S Floating or On/Off 35 lb·in (4 N·m) 60 Seconds at 60 Hz M9104-GGA-2S Proportional
35 lb·in (4 N·m) 60 Seconds at 60 Hz 48 in. (1.2 m) UL 444 Type CMP Plenum Rated cable with 19 AWG (0.75 mm2) conductors and .25 in. (6 mm) ferrule ends
M3 Screw Terminals
adjustable rotation time
Features
• two torques available: 18 and 35 lb·in (2 and 4 N·m) — offer the most suitable choice for the specific application
• short 30-second travel time available — provides a quick response for two-position zone applications • 35 dBA nominal audible noise rating — meets the audible noise requirements for open ceiling environments
• synchronous drive — provides a constant rotation time that is independent of the load
160
Get technical help from one of over 100 technical specialists.