This page contains a Flash digital edition of a book.
HEAT PUMPS SIMULTANEOUS HEATING AND COOLING


District system AM and PM loads – 4 May


200 180 160 140 120 100 80 60 40 20 0


Simultaneous load less than 50% of system capacity for short periods


charge a thermal store and release this to augment or provide the afternoon cooling and vice versa. The drawback of this system, however, is


Cooling kWh Heating kWh


Figure 5: Morning and afternoon loads with small periods of simultaneous loads


heat pumps. The same then occurs during the cooling cycle in the afternoon, where the following morning’s heating can be generated during the afternoon cooling process (see fi gure 7). Effectively, load shifting generates as


much energy as possible simultaneously, thereby hugely increasing overall system effi ciency. Use the morning heat load to


that the hydraulics of the heat pump may need to be separated from the LTHW and CHW systems as, by virtue of the three port valves, the fl uids from the ground array will pass to the LTHW and CHW. If there is a thermal transfer fl uid requiring antifreeze to protect the evaporator, this fl uid will be present in both the LTHW and CHW systems. This is an added installation and maintenance cost. A further drawback is the control strategy required to operate such a system. Generally, the heat pumps can only deliver one load to a controlled set point. For example, if the system is cooling dominant at a certain point in time, the heat pumps are programmed to deliver the load to a set point in cooling. The heating then provided by the condenser is effectively ‘uncontrolled’, in that the heat pump is not delivering this load to a particular set point. The building management system (BMS) must therefore identify how best to deliver this load and when, using the three port


Simple COP analysis Full heating or full cooling only Pumps and compressors 28 kW


Load 100 kW System COP 3.57


100 kW


Full simultaneous heating and cooling


Pumps and compressors 28 kW Load 200 kW System COP 7.14


Three port valves used to direct free cooling or free heating to the plate exchangers


Simultaneous capabilities using three port valves


100 kW 50 kW 0.75 kW


Heat pump evaporator ‘cold side’


50 kW 0.75 kW


12.5 kW input


HP 1


12.5 kW input


HP 1


50 kW 0.75 kW


Heat pump condenser ‘hot side’


50 kW 0.75 kW


Heat pumps control to either heating or cooling load and the opposite load is provided free by diverting three port valves. They do not ‘reverse’, they simply have a hot and a cold side


Ground array Figure 6: A simultaneous heating and cooling heat pump system with three port valves


56


CIBSE Journal November 2012


www.cibsejournal.com


00:30 02:30 04:30 06:30 08:30 10:30 12:30 14:30 16:30 18:30 20:30 22:30


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80