homogenous as they will contain small air spaces and materials that differ across each piece of masonry. However, in terms of thermal calculations, such ‘minor’ internal irregularities are normally ignored, and only considered for air pockets in insulating materials that may be large enough to allow air convection currents within the material, reducing the thermal resistance. (BS 10456[1] explains the method to undertake this analysis).


105mm brickwork


50mm eps insulation


(unidirectional) but will also pass sideways between the different materials. Since the simple U value calculation is based on unidirectional flow, this more complex heat flow pattern needs to be solved by computer methods (numerical analysis) or by applying the ‘Combined Method’[3]


. This method


uses the mean of two extreme values of thermal resistance (known as the upper,


RU, and the lower, RL) of the heat flow paths through the structure to provide the bridged


thermal resistance, Rb. The upper limit, RU, is the resistance that allows for simple unidirectional heat flow and is determined


by proportioning the resistances of the different heat flow paths with respect to their area. (And this calculation alone was the method used historically when calculating non-homogenous U values). The lower


13mm lightweight plaster


limit of thermal resistance, RL, is a value that allows for sideways flow of heat through the structure. The actual resistance will fall somewhere between the two extremes and a mean of the two values is taken as a reasonable estimate of the overall bridged


100mm light concrete blockwork Figure 2: Simple wall structure


So considering the brickwork layer, and referring to the data in Figure 1, the exposed bricks have an R of 0.105/0.77 = 0.136 m2


and the exposed mortar 0.105/0.94 = 0.112 m2


K/W. CIBSE Guide A recommends


that if the R values differ by no more than 0.1 m2


K/W then the R value for the major


element may be used (and in this case the difference is 0.136 - 0.112 = 0.024 m2 the R for this layer is taken as 0.136 m2 If the difference exceeded 0.1 m2


K/W), so K/W.


K/W, then


the layer is said to be thermally ‘bridged’ and a more complex procedure must be used (that will be described later). A general rule is that mortar joints can be treated as having insignificant influence[2]


when the thermal


conductivity of the masonry units is greater than 0.5 W/mK. If the concrete blockwork layer is examined


the light concrete block R = 0.100/0.20 = 0.500 m2


= 0.100/0.88 = 0.114 m2


K/W and the protected mortar R K/W. Clearly the


difference between the R values exceeds 0.1 m2


is that the flow of heat may not be assumed as going directly from one side to the other


58 CIBSE Journal June 2011


K/W and so the blocks are said to being thermally bridged by the mortar. The effect of a thermally bridged structure


K/W


resistance, Rb. The actual calculations appear complicated (especially where there are multiple bridged layers) but are actually quite straightforward (if sometimes lengthy). An example calculation for the wall in Figure 2 is given in panel 1. Elements in real constructions can be rather more complicated, having several non- homogenous layers. CIBSE Guide A3 2006 Section 3.11.2 has more extensive examples and several are available in “Examples of U-value calculations using BS EN ISO 6946:1997”[4]


freely available from the UK


government DCLG website. However it is not always easy to judge


how to approach the calculation and to know where simplifying assumptions can be applied. The excellent document ‘Conventions for U-value calculations’ BRE Report BR 443:2006 can be freely downloaded from the web and has clear and extensive guidance on the practical approach required when examining U value calculations for a whole range of real building elements. This information is particularly useful at the early stages of design when generic materials and construction techniques are envisaged. This not only includes guidance as to the elemental considerations (eg how to determine appropriate resistances for foam faced blocks, or plasterboard on dabs) but also how to establish the U value for constructions complicated by such things as recessed light fittings and loft hatches. BR 443 includes extremely helpful advice on factors to be


Figure 3: Lower section of example double glazed window with a frame manufactured from two principal materials (source http://windows.lbl.gov/ software/therm/images/therm2-1.gif)


considered when determining U values for walls, roofs, floors, glazing and doors. One of the concepts applied in BR 443 that


was introduced to CIBSE Guide A in the 2006 revision (and still unfamiliar to many) is that of the ‘linear thermal transmittance’, Ψ-value, or the psi-value (W/mK). This is used to establish the variation in heat flow that occurs at the junctions between the various building elements, for example where a wall joins a roof, or a piece of glass connects to a frame. Because of more complicated geometries and materials used at the junctions, the overall U value of the construction will be affected, and the Ψ-value represents the difference in heat flow through the junction compared to that through the separate connecting elements. This is illustrated by the unevenness of the temperatures across the lower section of an example window (Figure 3 and Figure 4) caused by the increase in U value at the junctions. The ‘cooler’ green area can be seen extending into the area where the inside pane of glass meets the frame. (Apart from the additional heat loss, this may cause problems with condensation and subsequent mould growth.) The practical impact may be investigated through thermal modelling or by applying tabulated values from the CIBSE Guide. A useful tool, ‘Therm’, may be freely downloaded from http://windows.lbl.gov/ software/therm, and will allow 2-dimensional analysis of building structures and windows, so that potential high U values may be avoided.


Psi-values are available for specific construction types, eg roof joints, floor to wall sections and glass to frame connections. Accounting for thermal bridging at edges has become increasingly important as the requirements for building thermal performance have become more stringent, and consequently the main elements have higher thermal resistances increasing the relative impact of losses at edges and junctions. The supporting documents to the


www.cibsejournal.com


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72