Wiring Accessories


Testing requirements and USB socket-outlets


As a wholesaler, are you having to deal with the frequent returns to your store of USB socket-outlets that have been faulty following insulation resistance testing? If so, Jake Green, head of technical engagement with Scolmore Group can shed some light on the issue.


W


ith USB socket-outlets, the charging unit is built into the back of the socket and this is sometimes fixed to the on position. This means that the switches on the socket that control the 13 amp plug element have no connection to the USB charging point, with the result that is permanently connected. This causes problems when carrying out insulation resistance testing, as the electronic components of the USB charging unit are part of the circuit and therefore the 500V that electricians use to


test them could damage those components resulting in a faulty charging port. The Click range of USB sockets has been designed to withstand the 500V insulation test due to the nature of the circuitry built within the USB socket.


Chapter 64 of BS 7671 details the general requirements for initial verification, and Section 643 deals with the requirements for testing. Here we briefly consider the requirements for insulation resistance testing and the care that should be taken when testing after second fixing has occurred.


Insulation resistance testing Insulation resistance testing is carried out to confirm that there are no inadvertent connections between live conductors, and between live conductors and Earth before the installation is energised (643.3.1).


The insulation resistance test is a ‘dead’ test, and the normal supply should not be ‘live’. To this end the person carrying out the test should ensure that the circuits to be tested are isolated and the normal power cannot be energised inadvertently.


The minimum required insulation resistance values in megohms is detailed in Table 64, although a value significantly in excess of these


24 | electrical wholesalerMay 2023 ewnews.co.uk Figure 1: Testing live conductors to Earth


Insulation resistance testing is carried out to confirm that there are no inadvertent connections between live conductors, and between live conductors and Earth before the installation is energised (643.3.1).


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44