Cable Management
Premature collapse of wiring systems
Jake Green, head of technical engagement with Scolmore Group, which includes the Unicrimp business, provides details of the general requirements of Regulation 521.10.202.
A
ſt er several tragedies, Regulation 521.11.201 (AMD 3 BS 7671: 2008) was introduced; its purpose being to limit
the risk to fi refi ghters from entanglement by cables when they entered or exited a prem- ises.
This regulation has now been renumbered as 521.10.202 but remains essentially the same except for the removal of any reference to escape routes. It now reads: “Wiring systems shall be supported such that they will not be liable to premature collapse in the event of a fi re.”
This requirement should not be confused with the recommendations of standards like BS 5266-1 (emergency lighting) and BS 5839-1 (fi re detection and fi re alarm systems), which recommend methods of cable support to maintain circuit integrity during a fi re.
Escape routes and BS 7671
The original regulation referred to escape routes, and this generated a level of confusion: ‘How should escape route be defi ned?’ BS 7671 defi ned escape routes diff erently to that used in other guides, regulations, and legislation. For example:
BS 7671 – ‘Path to follow for access to a safe area in the event of an emergency’.
Building standards technical handbook - … means a route by which a person may reach a place of safety…’.
Approved Document B in England and Wales -…that part which a person has to traverse before reaching either the safety of a fi nal exit or the comparative safety of a protected escape route…. The removal of ‘escape routes’ from the regulation now means that it applies to all areas of the installation.
Premature collapse There is no specifi c defi nition of ‘premature collapse’ to be found in Part 2 of BS 7671. One dictionary defi nition of ‘premature’ is, ‘occurring or done before the usual or proper time: too early’. Since the purpose of Regulation 521.10.202 is not to maintain the critical signal path, rather to limit the risk to fi refi ghters; premature collapse should be considered in relation to that single purpose. Electrical contractors, network installers and the like are not best able to judge how fi res behave, the likely temperatures that will be attained, nor how fi refi ghters will carry out their role within a
premises that is on fi re. It is important therefore, that electrical contractors and other installers give due consideration to the support given to wiring systems to provide maximum reasonable application of Regulation 521.10.202. Scolmore group company, Unicrimp, off ers a comprehensive range of cable accessories within its Q-Fire fi re-rated range that are designed to provide the necessary protection from premature collapse. There is a great deal of responsibility placed on contractors to apply Regulation 521.10.202, not because they want to meet minimum expectations, but rather because they want to protect fi refi ghters who are working under extremely dangerous conditions.
An electrical contractor should consider, as a minimum, the following: • Wall fi xings – careful consideration should be given to the mass of the wiring system that is to be supported (including the trunking, cable tray, etc. with the cables in situ). Will the structure of the building maintain suffi cient fi re resistance to permit cables to avoid the need for metallic supports? Will such supports be suffi cient if fi refi ghters damage ceilings when applying water?
• Cable clips – metallic clips are essential as indicated by Note 3 and 4 of Regulation 521.10.202.
• Brackets or internal clips for PVC trunking – to keep the lid or cables in place (see Note 3 of Regulation 521.10.202).
Conclusion
Electrical contractors should carefully consider their responsibilities when installing wiring systems. Under fi re conditions, failure to make the right installation choices may lead to serious consequences.
ewnews.co.uk February 2025 electrical wholesaler | 29
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44