TRANSDUCERS, TRANSMITTERS & SENSORS ANALYSIS HIGHLIGHTS IMPROVEMENTS


The trial generated accurate, reliable results for detecting trace-level impurities and chlorine with Bürkert's 8905 analysis system and sensors.The repeated accuracy of the data is enabling investigation of wider plant automation


An analysis system trial using Bürkert sensors at a water treatment plant has shown its ability to reduce downtime


B


ürkert's client, an enivronmental monitoring service company, was tasked to run a water analysis trial at a


gas power plant in Ireland. Steam, generated from ultra-purified water, is required to drive the plant's turbines. Water fed from a semi- covered reservoir passes through a treatment plant featuring a reverse osmosis (RO) system and an electric deionization (EDI) process, which create the required ultra-purified water. Water conductivity from the process has to be accurately measured and reduced to approximately 15 µS and the RO system is tasked with the removal of impurities, which can deteriorate the EDI over time. Impurities penetrating the RO system can also cause stress corrosion cracking in the turbine blades. The environmental services


company was required to report on the water treatment plant's conductivity as well as levels of chlorine, pH, ORP and turbidity. The plant's existing analysis equipment didn't provide sufficient data for the site’s needs. The company selected Bürkert to provide the sensors and water analysis capability as a result of the company's expertise in rapid, accurate and reliable measurement. A full suite of Bürkert 8905 Online Analysis


System units for monitoring water parameters, combined with Type MS sensor cubes, each suited to monitor a specific characteristic, were installed into a compact panel. The trial


monitored the feed into the RO system and while it was originally designed to run for three months, as a result of the Covid pandemic, the sensors were left in place for six months. The challenge of the reservoir's low flow was


a result of its oversized construction. Designed for a maximum capacity of 50 tonnes of water per hour to support hours of peak power generation, the plant can process as little as 20 tonnes per day when on standby. Typical analytical sensors on a one-inch process line require 2-3,000 litres per hour, whereas Bürkert's 8905 system, even with five sensors, requires just 30 litres per hour. Even when a continuous pump is required to fulfil the sensors' minimum flow requirement, the Bürkert system provides reduction in


wastage and cost. Throughout the six-month period, the


system ran without deviation, not requiring recalibration or inspection, which demonstrated its reliability. This was a crucial requirement, giving confidence for uninterrupted service and low maintenance requirements. Crucially, the accuracy and


sensitivity of the 8905 system showed chlorine trace not previously


identified. Long term, trace levels of chlorine can degrade the RO membranes and ultimately allow the unwanted passage of chlorine through to the EDI, which it can also damage. Furthermore, the customer wanted to avoid any flow of chlorine back into the river system. A carbon filter can now be used upstream of the RO to prevent the inbound flow of chlorine.


Bürkert's 8905 water analysis system and chlorine sensor (below) has a t90 time, the duration that it takes the sensor to measure 90% of the chlorine concentration, of less than 30 seconds


For detection accuracy, Bürkert's 8905 water


analysis system and chlorine sensor has a t90 time, the duration that it takes the sensor to measure 90% of the chlorine concentration, of less than 30 seconds, whereas typical industry standards for chlorine sensors have a t90 time from 60 to 180 seconds. The fast reaction time also means that the


8905 sensor is unaffected by polarization, whereby a sensor measuring zero chlorine for long periods of time can take several hours to react and measure with reliability when small amounts of chlorine are reintroduced. Typical sensors can therefore be unable to measure trace chlorine levels, which can pass through the system before they are able to react. Instead, Bürkert's 8905 sensor is able to accurately and reliably measure chlorine even at µg/l trace level. Cost was also reduced in system


installation. The 8905 system can be installed into a single compact panel, approximately one meter square, as opposed to utilising several larger boards, complete with transmitters. This reduces wiring costs and installation time, as well as footprint. The potential for Ethernet connectivity for plant automation will also reduce the cost of sensor outputs and increase the ease of system integration. The system can be operated by the seven-inch touch display or remotely using Bürkert's Communicator PC tool. The results of the trial have identified accurate, repeatable and reliable readings across the analytics, and highlighted the potential for a more effective water treatment system.


Bürkert Fluid Control Systems www.burkert.co.uk


MARCH 2021 | PROCESS & CONTROL 31


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64