Phil McEneaney, from Stulz UK, warns that a failure to understand the difference between comfort cooling and precision cooling, is resulting in poorly specified equipment – leading to higher costs, IT failures and increased business risk
operations. With emerging trends such as 5G, IoT, automated vehicles and digitalisation in the industrial sector, there will be a dramatic increase in remote edge data centres and smaller, server rooms reliability will be critical. But are installers of cooling solutions prepared for these developments? A lack of awareness of the differences between comfort cooling and precision cooling is impacting the reliability of IT infrastructure, resulting in serious consequences for businesses. Comfort cooling units are designed for cooling people in offices and retail environments. This type of cooling technology is intended to operate for short periods of time (of around five hours per day, five days per week) and the typical life expectancy for a unit is around five years. Precision cooling, on the other hand, is designed for use in technical environments, 24/7, and the typical life span is much longer, usually between 10 and 15 years.
P Temperature accuracy
Stulz UK’s precision air conditioning units ensure optimum temperature accuracy with maximum tolerances of +/- 1 °C and are designed to dissipate isolated thermal loads even from distant corners of the data centre. Comfort units, on the other hand, can normally deviate from the set value by as much as +/- 3 °C. This is significant, as information and communication technology only works reliably and without faults within a relatively narrow temperature range. There are other important differences that also need to be understood, however.
Comfort cooling units, as part of their design, are made to cater for ‘latent heat’. Environments that are populated by people (as opposed to technical equipment) produce this type of heat, which contains moisture, while technical spaces (such as server rooms) radiate pure heat – referred to in the industry as ‘sensible heat’. A comfort cooling unit will have a typical ‘sensible heating ratio’ of between 0.5 and 0.6, while a precision unit will have a sensible heat ratio of one. Comfort cooling units, which are designed to remove the moisture produced in retail and office spaces,
oorly specified cooling technology can result in erratic climate control, increased operating expenditure, and costly disruption to IT
can use up to 50 per cent of their energy for dehumidification. This is an important difference – precision air conditioning units convert more than 95 per cent of the energy used exclusively into cooling capacity. Therefore, the technology required to achieve this pays off quickly in terms of lower operating costs.
A comfort cooling unit rated at 10kW, with a sensible heat ratio of 0.5, will only deliver 5kW of sensible cooling. A precision cooling unit, with a heat ratio of one, on the other hand, will deliver the full 10kW. This means you may need to specify two comfort cooling units to deliver the same capacity as one precision cooling unit.
Total cost of ownership
There are significant risks associated with inappropriate use of comfort cooling units, which installers need to be aware of. Unlike comfort air conditioning units, precision units feature strictly controlled and accurate dehumidification (tolerance +/- 5 per cent relative humidity), as too much humidity can lead to condensation and corrosion, while too little can cause static charges, data loss and damage to hardware.
If you are removing moisture from the air, via a comfort system, you must be aware that the air will become drier and this can lead to static build-up in the technical space. These static shocks can be quite powerful and lead to failures of sensitive electronic equipment. We have seen instances where comfort cooling units have been specified, and the client has had to purchase additional equipment to add moisture to the room. Humidification units add an extra layer of cost to the original installation and are very expensive to run – which ultimately increases the total cost of ownership of comfort cooling solutions. Other factors also contribute to increased expenditure and a replacement compressor may be needed after as little as three years, if the unit is run day in, day out, as comfort units are not designed for this level of continuous operation. Precision cooling units with EC fan technology can also offer further savings in running costs. The technology consumes up to 30 per cent less energy than a conventional three-phase fan; precision units (such as the MiniSpace EC range) can also run in energy-saving partial load mode and have a high motor efficiency of up to 92 per cent. It is a ‘false economy’ to prioritise capital outlay when specifying air- conditioning units: If you install a solution that isn’t appropriate for the technical environment, you will have issues. Effectiveness needs to be the primary consideration, along with the long-term operating costs.
Operating features: comfort vs precision
uStulz Minispace 8 BUILDING SERVICES & ENVIRONMENTAL ENGINEER MARCH 2019
Importantly, there is no ‘fall off’ in capacity on long pipe runs, which is an advantage over comfort cooling systems. Pipe runs can affect the efficiency of the cooling system, so this is an important consideration when specifying a solution. Also, the water collected by comfort cooling units needs to be disposed of and pumped to a drain – this presents further challenges, as there is a potential risk of
DATA CENTRES Poor knowledge of cooling leads to business risk
leaks or flooding in the server room, which could result in significant damage to electronic equipment. Air filtration is another important factor when comparing comfort versus precision cooling. Precision air conditioning units (such as those manufactured by Stulz), filter and circulate three times the amount of air as comfort units with the same rated capacity.
Other differences are also important to note – for comfort cooling applications, it is less important for the filter to be highly effective in removing small particles; dust circulation has no detrimental effect in a non-technical environment. In data centres, it is crucial to prevent particles being blown or sucked into technical equipment, as this can shorten the lifespan of IT assets.
Advanced precision cooling units can provide continuous monitoring and control of air filtration to ensure high availability. In the case of the Stulz MiniSpace EC range, an alarm notification can be raised via mobile phone or through the building management system. This helps businesses ensure the resilience and availability of their IT operations at all times.
Conclusion
Ultimately, data centres and rooms subject to high thermal loads need constant climatic conditions in order to work reliably. Fluctuating temperatures, humidity and dust jeopardise both function and data stocks. Precision cooling technology is specifically designed for server rooms and technical environments where reliable thermal optimisation and high availability are crucial business imperatives. As the number of remote edge data centres and localised server rooms increase, it will become particularly important to understand the differences between ‘precision’ and ‘comfort’ when applying cooling for these systems. Many specifiers and installers fail to appreciate the impact of employing inappropriate cooling technology until it is too late; there is an urgent need for further education to avoid costly mistakes and to prevent the risks associated with poor climate control.
www.stulz.co.uk Read the latest at:
www.bsee.co.uk
uStulz Air distribution with speedcontrolled EC fan technology
‘
There are
significant risks associated with inappropriate use of comfort cooling units, which installers need to be aware of
’
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44 |
Page 45 |
Page 46 |
Page 47 |
Page 48