• • • PANDUIT • • • Short-circuit mitigation to


safeguard life & minimise damage Whether the electrical power infrastructure application is data centre, industrial development or enterprise, an electrical short-circuit is a major cause of concern when power outages can cause disruption to the capabilities of the site


D


ata centres require large scale provision of electrical distribution systems which are designed to power equipment safely


and reliably.


Electrical flow problems, such as short-circuits, can cause major damage both thermally and electro-dynamically to equipment, supply cables and human life. The disruption to the facility from an outage could shut down operations for a costly length of time.


Short circuits can happen anywhere along the electrical distribution system. The fault occurs when an abnormal connection between two nodes of an electric circuit is made. Panduit research informs us that during a short circuit event, maximum electromechanical stress between conductors occurs at or before 0.005 second. Current levels in these events can reach 200kA.


In the worst case of a 3-phase short, magnetic field induced repulsive forces between cables can range upwards of 10,000-pounds. Typical circuit- breakers trip and interrupt a fault between 0.06 to 1.0 second, allowing time for substantial damage to occur.


Cable cleats reduce damage and expensive rework by performing their function within those first 0.005 second, at peak kA, before the circuit breaker trips. Cleats restrain cables during their most violent contortions, reducing damage and avoiding personal injury. Panduit cable cleat systems include cable trays for additional flexibility in the design and installation of engineered solutions to short circuit events.


What is a cable cleat?


As defined by IEC 61914:2021 Cable Cleats for Electrical Installations, it is a device designed to provide securing of cables when installed at intervals along the length of cables. However, how reliable are cable cleats in damage prevention. To gain certification, due diligence is required, and external testing of cleats is performed, which is a necessary and expensive process to validate a cleats capability. Panduit has developed an industry award winning computer simulation programme which predicts the outcomes of the material composition of cleats and the forces present in short circuit fault. This allows Panduit to test up to intentional failure at higher voltages to validate the simulation and helps define the strength capabilities of the cable cleats. These are then officially tested by KEMA to demonstrate the efficacy of the simulation and the actual cleats. To simplify the cleat selection process Panduit provides a cleat calculator on its website. For example, when specifying cleats for trefoil cable layout, two variables need to be known: Peak short circuit fault level (kA), and cable outer diameter (OD in mm).


Using this data, force between conductors during short circuit event can be calculated and the correct cleats at appropriate spacing can be determined, see image. The results provide cleats that pass regulations providing clear and simple guidance and saving time in cleat selection.


22 ELECTRICAL ENGINEERING • FEBRUARY 2023


electricalengineeringmagazine.co.uk


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52