ASSET MANAGEMENT | EDGs


Monitoring for emergency diesels


Monitoring systems for emergency diesel generators can boost plant performance and optimise operations. By Manuel Güldner and Günter Rott


A SAFE AND RELIABLE EMERGENCY power supply is required to operate any nuclear facility. The primary function of the emergency diesel generators (EDGs) is to supply the emergency power required during a loss of offsite power (LOOP) and to guarantee the required voltage and frequency during the emergency power mode. Accordingly, nuclear power plants must have a reliable


emergency power system on standby. This reliability can only be achieved if the physical condition of the diesel generators is checked and monitored frequently. Such monitoring helps to anticipate maintenance needs and avoid time-intensive repair work. Permanent monitoring systems help to collect equipment data that can be analysed to make informed decisions about further action. In several cases, a single measurement does not give a clear indication of an issue. Consistent monitoring is needed to analyse trends and characterise the complete behaviour.


What is a monitoring system? In general, there are two categories of monitoring systems


Manuel Güldner


EDG product portfolio manager, Framatome


for emergency diesel generators: ● Those required under nuclear safety standards (KTA 3702 (2014-11); Emergency Power Generating Facilities with Diesel-Generator Units in Nuclear Power Plants) for operation of the generators.


● Those that are not mandatory for operation but improve the complete handling of the component itself.


Günter Rott


EDG design lead engineer and technical expert, Framatome


According to nuclear standards, a safety-relevant qualified generator set (genset) is required on site. It must have had several running hours in the supplier’s facility and during commissioning. It must have regular test runs (typically monthly) that follow the same principles and test procedures that, with the corresponding monitoring, enable a strong basis for a comparison and respective analysis of the behaviour of the genset or of the single auxiliary components in the nuclear power plant. The monitoring can be based on measurement


parameters such as temperature, vibration, pressure, level, speed, start behaviour or electrical values (active power, voltage, current, cos phi, etc). To evaluate the correct conclusions of each parameter,


continuous monitoring of the measured values is required (known as condition monitoring). Additional functionalities increase the quality and efficiency of the monitoring tasks. These functionalities include further parameter processing (such as experts’ logic, fast Fourier transform (FFT) analysis, maximum/ minimum comparisons, calculations, surveillance of limit thresholds, etc.), visualisation, and automatic data mining and reporting.


18 | November 2021 | www.neimagazine.com The measured values of the parameters listed above


can be recorded in a customised manner and enable pure data recording and visualisation, which provides a basis for further analysis and actions. This information also offers insight into the instrumentation and control (I&C) of the unit and the plant. It is also possible to compare measured values from various test runs of the same and multiple types of diesel generators to detect degradation. A monitoring system that is independent of the original equipment manufacturer also offers the advantages of a uniform system platform, which can be used for a variety of emergency power systems. Several types of generator sets may be used in one facility.


Why is it beneficial to have a monitoring system? Although the monitoring system is not mandatory for operation of the emergency diesel generators, it offers several advantages. In some circumstances a monitoring system will be recommended or even required for finding a solution, or example if damage has occurred that could have been avoided by observing specific trends or identifying defects in which the root cause is not known. A monitoring system can be implemented at any time.


The advantages include: ● Understanding equipment condition. Monitoring data


provides useful information about the behaviour of equipment. For example, if there is concern regarding the behaviour of bearings, it can be checked easily by comparing the temperature measurements from the last tests with the different divisions. Performance and condition trends can be checked and appropriate measures, such as more detailed examinations or maintenance work, can be scheduled. This knowledge also supports discussions between the nuclear authority, plant owner, supplier and equipment manufacturer.


● Facilitating operational processes for monthly tests. A permanent monitoring system reduces setup times for logging monthly tests. Data are recorded continuously and independent of events, so different data sets can be accessed in a time-definable manner to evaluate events. Uniform and generically formulated protocols ease preparation, execution, and completion of the test runs on-site. The maintenance team can focus on the goal of conducting the operational tests.


● Efficient troubleshooting. A detailed alarm and event list with dates and timestamps enables faster, easier and more precise troubleshooting. This can reduce the downtime of the gensets. The monitoring system can help the plant owner identify the root cause of problems with the equipment. For example, with fatigue issues, it


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45