protection against
The best fire
a u t o m a t i c sprinkler systems
requirement for testing and routine maintenance to be carried out. The end users have a responsibility to arrange a specialist to carry out this work.
UK Standards
In the UK, sprinklers in non-residential premises should be designed, installed and maintained in accordance with BS EN 12845. Some systems may be installed to other international standards or to those specified by FM Global. The Standard recommends that the testing, servicing and maintenance be carried out by the system installer or a similarly qualified company.
Given that a sprinkler system not only protects property but life and is often ‘mission critical’, the value of following appropriate procedures cannot be over-emphasised.
Types of sprinkler systems
There are a number of different types of automatic sprinkler systems; they have different uses and applications.
A wet-pipe system is where all the pipes leading from the water supply, through the various control valves and on to the sprinkler heads, are permanently filled with water under pressure.
Wet-pipe sprinkler systems are the most common type installed. They are used in heated buildings, where there is no possibility of the water freezing, i.e. where the ambient temperature remains above 5 deg C. Wet systems are capable of delivering water to the fire as soon as a sprinkler head operates.
Dry-pipe sprinkler installations are appropriate for applications either where there is a danger of the water in the pipes freezing or in situations where there may be temperatures above about 70ºC. In a dry-pipe system the pipes on the ‘active’ side of the installation control valves are charged with air which is under sufficient pressure to prevent the entry of water into the delivery pipework. Once the first sprinkler head operates, the compressed air escapes through the head and water follows.
A pre-action sprinkler system is a dry-pipe system linked to an automatic fire detection system which protects the same area.
Operation starts when a heat or smoke detector in the detection system activates (which will usually happen more quickly than a sprinkler head). At this point a ‘pre-action’ valve opens to allow water to flow into the sprinkler pipework before the first sprinkler head operates. Discharge of water will not occur until a sprinkler head operates. This type of system is quite often used in water-sensitive areas such as electrical equipment rooms and computer suites.
Deluge systems are commonly fitted with open nozzles or projectors and are triggered from air/water detection lines or some kind of detection system.
Deluge systems provide water to a network of open nozzles which could be for local application or protection of a specific high-risk plant area. Other risks would include such situations as tanker loading bays, flammable gas tanks, oil storage reservoirs, oil lines, power generation plants etc.
Who is responsible after installation?
Once a sprinkler system has been handed over to its owners, the responsibility for the equipment will rest with them. Whether or not the system will operate as designed when required will depend on whether the correct maintenance procedures are carried out. Article 17 of the Regulatory Reform (Fire Safety) Order 2005, which came into effect in England and Wales on 1st October 2006, imposes significant liabilities on the ‘responsible person’ (read employer or property owner) who fails to maintain fire safety equipment (including sprinkler systems) intended for the protection of life from fire.
Sprinkler systems in the United Kingdom are generally designed and installed to European and British Standards. The standards set out a
© CI TY S ECUR I TY MAGAZ INE – SUMME R 2 0 1 9 www. c i t y s e c u r i t yma g a z i n e . c om
Required testing and maintenance Weekly:
• Testing alarms • Pump/engine test and exercise compressor • Check valve positions.
Quarterly:
• Review of hazard • Inspection of pipework/supports •Water supply flow tests • Exercise stop valves • Test flow switches.
Six monthly:
• Valve service/inspection • Fire brigade electrical central station check.
Annually:
• Pump service • Check tank ball float valves • Engine service • Valve service/inspection.
3 Yearly:
• Inspect tanks • All valves & non-return valves • Inspection, service and overhaul as necessary.
Other Intervals:
• Tank drain-down & clean – 10 yearly • 25 Year Sprinkler head performance testing / system inspection.
There is little doubt that sprinklers are inherently reliable and have a well-deserved reputation for controlling or suppressing fires in buildings and that effective design, installation and maintenance are required to sustain this reliability.
Steve Betts MSyI
Business Development Director and Kerry Solomon, Operation Director
Hall & Kay Fire Services Ltd.
www.hkfire.co.uk
>
23
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40