PNEUMATIC TUBE SYSTEMS


It is rather like driving a car with the warning indicators illuminated. Yes, the car may continue to drive – but that does not mean it is safe to do so.


New Hospital Programme – BMS integration The New Hospital Programme requires a far more advanced interface with the pneumatic tube system control system. Without doubt, this will provide a much more centralised monitoring facility for personnel working within the Command & Control Centre. But unless the people monitoring – and potentially reacting to – faults relayed by the PTS are familiar with the system itself, the new interface remains little more than an alarm bell. It is no more informative than medical staff calling the helpdesk to say that the PTS is not working. That situation can be improved through training. Many faults can be resolved simply by understanding


what the system is reporting. A call to a ward or department may solve that the problem which is a user issue, such as an overfilled basket or another straightforward obstruction. The challenge becomes greater when the control


system servers themselves are located within tray-mounted stacking modules in the Command & Control Centre. This raises practical questions about how FM personnel and PPM contractors will access the PTS control system and, importantly, who will have responsibility for responding to the information it provides. FM teams need access at all times, as will the PPM contractor. Traditionally, a control computer located within the main


hub or plantroom has been a practical solution. It provides direct access to the system where the equipment itself is located, rather than placing the primary point of access in a remote control room. System or mechanical faults require two things:


analysis and reaction. Clear lines of responsibility and demarcation are therefore needed to prevent somebody in a control room simply resetting faults to get a zone running again. In many cases, unless the underlying problem has been addressed, the fault will simply repeat. There is arguably no greater practical advantage in having access to the PTS control system from a Command


Pneumatic tube systems have been used in hospitals for many years, historically beginning with very simple, single-line systems connecting two departments – for example, the Emergency Department and the laboratory.


& Control Centre than there is through a secure remote connection when it comes to gathering diagnostics. The important issue is not where the screen is located. It is whether the person looking at it understands what they are seeing and knows what action should be taken. Otherwise, it remains only an alarm.


Alarm interpretation Having answered many thousands of calls to our around- the-clock PTS helpline for hospital clients, one thing has become particularly noticeable: nothing is so simple that it cannot be misunderstood. Our instructions when calling for assistance are clear.


We need a description of the problem and, importantly, what is being displayed on the control system. If a zone or station is in fault, the real-time software indicates why the section has been suspended and where the fault is occurring. But if the call comes through a hospital helpdesk rather


than directly from FM, we can sometimes get what might be called the ‘A&E syndrome’. A&E has one of the most heavily used PTS stations in a


hospital, particularly within A&E Majors. This single station can contribute between 20 and 35 per cent of site-wide traffic flow because of two factors: the number of samples being taken and the fact that A&E operates 24/7. If an A&E staff member sees an alarm on their PTS station, they may call the hospital helpdesk and report that the A&E station is broken.


November 2026 Health Estate Journal 45


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72