PHOTOELECTRIC SYSTEM SMOKE DETECTOR COMPARISON CHART Edwards/Kidde
Part Number Voltage Range Thermal
15.2 ED-KIRPD ED-KIRPHD 15.2
to19.95 VDC
to19.95 VDC
No Yes 4-Wire 2 or
Standby Current
Alarm Current
Relay Aux
Direct Wire/ Plug-In Head
2-Wire 51uA 68uA No Plug-In 2-Wire 51uA 68uA No Plug-In
Functional Test Method
Smoke Smoke
NFPA Sensitivity Test Method
Built-in Circuitry Built-in Circuitry
Comments/ Notes
Listings & Approvals
1,2,3 1,2,3
Smoke Detector Testing NFPA 72 requires functional and sensitivity testing on a regular basis. ADI provides products for this requirement. “Tests shall be performed to ensure that
each smoke detector is within its listed and marked sensitivity range.” NFPA 72-2007 Chapter 10 (10.4.2.2 13g)
“Each detector shall be tested to confirm that it is within its rated operating range.”
CAN/ULC-S536-04, 5.7.4.1.3
APPROVAL LISTING 1 = UL, Underwriters Laboratories 2 = ULC, Underwriters Laboratories of Canada 3 = CSFM, California State Fire Marshall 4 = MEA, New York City 5 = FM, Factory Mutual 6 = BFP, Chicago 94 For orders, call 1.800.233.6261| For Systems Design Team, call 1.800.234.7971| Go To ADIGLOBAL.COM/US