HEAT PUMPS
might seem surprising – especially in the Northern Hemisphere – the science behind it is rigorous. Although we might feel that water at 5°C is quite cold, in thermodynamics, harnessing a river at 5°C is more about the grade of heat. We can quite comfortably take the 5°C from the water into the heat pump and return it at 2°C - this is enough for the heat pump to operate and in fact, a considerable heat gain. By using this temperature difference we are able to abstract water from rivers and oceans and use this to boil off the refrigerant in the evaporator and then compress the gas to 110°C which allows us to produce up to 85°C hot water. What’s more, the quantities of water being cooled are such that the overall effect on the river and the aquatic life within it is negligible; What’s more, the reality of global warming means that any reduction in river temperature (no matter how small) is actually beneficial for the environment. Generally speaking, there are three distinct types of heat pumps: those which abstract water via an open loop, closed loop or break loop. Open loops abstract the water directly into the heat evaporator, while closed loops utilise coiled pipework with a glycol solution that is positioned on the riverbed. Meanwhile, break loops send the water to a heat exchanger, where a glycol loop awaits it on the other side, thus precluding direct contact between the water and the evaporator.
Open loop systems are the most efficient heat pump option but can present some challenges as the river water might be saline, contain mussel seeds, silt or biological growth. However, these issues can be easily removed with the right upfront filtration and automatic chemical-free cleaning systems.
How does the underwater element of the heat pump function? There are many practical factors to consider when deciding upon the location of a river water ammonia heat pump, since the depth, flow rates, tidal fluctuations and ownership of the body of water will all have a bearing on its positioning and performance. What’s more, keeping it clean from silt, sediment and microscopic river life is a priority, with mussels and mussel seeds (which can measure 20 microns, or 0.02mm, in length) some of the toughest challenges to overcome. To do so, the heat pump carries a number
of filters with self-cleaning functions which remove impurities from the water and keep it in a serviceable condition. For starters, there is an initial woven mesh filtration system 1mm in diameter, which is self-cleaning through its automatic back-flushing feature and carries an inflow rate of below 0.4m/s in order to protect the endangered eel population and comply with regulations. The abstraction pump itself contains a
separate, self-priming vacuum pump and is equipped with variable speed capabilities. In theory, the pump could be capable of a vertical uplift of as much as ten metres, but in practice, it’s likely to achieve a more modest five or six metres due to the pressure, flow rates and other variables in the environment. Nonetheless, operators should remember that a shorter distance between the pump and the evaporator will incur reduced overheads in the long run. To combat the problem of mussel seed
ingress, a spinning drum inside the mussel stops generates a mild G-force of around 10RPM, which is enough to deter growth or inflow of the organisms. Filtered detritus is collected in a basket at the base of the system and returned to the river after a pressure differential triggers its release. Meanwhile, the heat exchanger is fitted with titanium tubes and super duplex end boxes to provide maximum protection against the rigours of the environment. It’s particularly prudent to spend more on quality materials for this equipment, since cutting corners now will inevitably cost more further down the road. A third form of protection is applied to
the spray chiller. This is in the form of an automatic tube cleaning system. This system sends rubber balls (slightly bigger than the tubes) to the end box where they are pulled through the tubes, essentially wiping the inside clean with the dirt going back into the river.
How does the heat pump operate? To simplify matters as much as possible, it may be helpful to break down the heat pump into its constituent parts. These consist of a shell-and-tube style evaporator and the outside of the tubes which are sprayed with ammonia which then evaporates as it removes the heat from the river water. The electric motor which powers the system could be air-cooled or water-cooled – as long as there is an option for the captured waste heat to be utilised. Although it would be ideal to
Download the ACR News app today
retain and reuse excess heat from the motor, this is not always possible.
As a company Star have a long history of using many different compressors depending on what is the best fit for each specific project. Currently, for the large capacity, open loop, high temperature heat pumps twin screw compressor are the best performers. As for the hot water heat exchangers, these consists of a plate-and-shell construction which offers the advantage of compact dimensions and higher pressure ratings. The desuperheater, condenser and subcooler are all standard installations, while the oil cooler is the most complicated component and careful consideration to ensure the right temperature profile for the oil to perform its function inside the compressor must be given.
The final piece of the jigsaw is the district heating network where the heat generated will be delivered and consumed. In order to achieve maximum efficiency and enhance economic savings through reduced OPEX, it should be remembered that closing the gap between the river water temperature and the heating requirements of the district is a worthwhile goal. In fact, for every 1K reduction in delivery temperature, a 1.5% increase in coefficient of performance (COP) can be achieved. Also, for every 1K the network ΔT is widened another 0.5% efficiency can be gained. These gains result from the compressor having to work less to close the gap between evaporating and condensing while the wider ΔT allows for the increase of the subcooling effect.
What other practical considerations are there? In order to truly optimise all facets of a river water ammonia heat pump system, it is advisable to take a strategic approach to its operation. That means trying to minimise all waste energy; we’ve already touched on the desirability (but occasional impossibility) of capturing excess heat from the system, but the cold streams generated by the heat pump could also be diverted to provide cooling or chilling facilities in data centres, hospitals and other buildings.
Another aspect to consider is the tariff pricing system and how it varies throughout the day. Savvy operators can take advantage of the most favourable tariff prices via the use of thermal storage, by switching the system off when electricity is expensive and turning it back on when the price falls.
www.acr-news.com • July 2022 19
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10 |
Page 11 |
Page 12 |
Page 13 |
Page 14 |
Page 15 |
Page 16 |
Page 17 |
Page 18 |
Page 19 |
Page 20 |
Page 21 |
Page 22 |
Page 23 |
Page 24 |
Page 25 |
Page 26 |
Page 27 |
Page 28 |
Page 29 |
Page 30 |
Page 31 |
Page 32 |
Page 33 |
Page 34 |
Page 35 |
Page 36 |
Page 37 |
Page 38 |
Page 39 |
Page 40 |
Page 41 |
Page 42 |
Page 43 |
Page 44