68 MOTORS AND DRIVES


Low harmonic drives ease stress on the power supply


Gregers Geilager explains how low harmonic drives continuously regulate the network and load conditions without affecting the connected motor.


T


he mains voltage supplied by electricity utilities to homes, businesses and industry should be a uniform sinusoidal voltage with a constant amplitude and frequency.


This situation is no longer found in mains grids. This is mainly because consumers take non-sinusoidal current from the network or have a non-linear characteristic, eg frequency converters, switching network parts or energy-saving bulbs. Because of the ever increasing use of non-linear


loads deviations becomes increasingly serious. Irregular power supply reduce the lifetime of motors and other equipment, and cables and transformers must be oversized to maintain proper operation. The compatibility levels of the standards EN50160/


EN61000 and, for industrial environments, EN 61000, apply within the scope of the EMC directives. It is assumed in principle that when these levels are


observed, all devices and systems fulfil their set functions without disruption in electrical supply networks. The distortion of the sinusoidal curve shape of the


supply network as a result of the intermittent use of electricity by the consumers connected to it is called ‘network feedback’. Experts refer to the relative harmonic content of a network on the basis of Fourier analysis and calculate


it to 0.5 kHz, corresponding to the 50th harmonic oscillation. The commonly used B6 bridge of an input rectifier generates a typical harmonic load of this type on the mains network, as does the use of energy-saving bulbs, TV sets, computers, phase-control systems and many other devices and systems. Excessive distortion causes malfunctions and even the destruction of electronic control systems, computers and control devices. High harmonic contents cause an overall lower


network efficiency, load idle compensating systems and may even cause their destruction.


Reducing feedback


Feedback from electronic power control systems can be reduced. In Danfoss frequency converters (except VLT Micro Drive), it is as standard limited by built in filter elements. If it is necessary to reduce the harmonic content in the mains network further, for example in case of weak networks or emergency power operation, a network analysis can indicate appropriate measures. Active filters and active front ends are very effective


in reducing harmonic oscillations up to 2kHz, and are used in addition to passive harmonic filters. For active filtering considerations must be given


to the effects above 2kHz, generated by these filters themselves. They make further measures necessary to keep the mains supply clean. Standard limits in this higher frequency range are still at the planning stage. The switching frequencies of active filters will cause


a peak at the switching frequency of the filter itself. This is above the range of current norms, but higher orders disturbance is of equal importance. Users should ask manufacturers about emission values and counter- measures to secure the operational safety of their plant. To avoid overloading and secure mains voltage


quality, a number of reductions, avoidance or compensation methods can be used with systems and devices producing harmonic currents. You can use the VLT Harmonic Calculation Tool to include specific counter-measures in the planning stage and therefore ensure the quality of your system. The network feedback of electronic devices can be calculated to within 0.5kHz, depending on the system configuration and standard limits. The operation of a plant supplied with a generator


Fig. 1. The upper red curve indicates the odd-shaped current curve produced by a frequency converter. Adding current in the shape of the green curve will re-establish the ideal sinusoidal curve.


can also be reliably simulated. Conversion of the network to generator operation is possible and takes the emergency power supply situation in account. Current standards (EN50160) are included in the analysis. At www.hcs-software.danfoss.de you can get quick


www.engineerlive.com


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84