search.noResults

search.searching

dataCollection.invalidEmail
note.createNoteMessage

search.noResults

search.searching

orderForm.title

orderForm.productCode
orderForm.description
orderForm.quantity
orderForm.itemPrice
orderForm.price
orderForm.totalPrice
orderForm.deliveryDetails.billingAddress
orderForm.deliveryDetails.deliveryAddress
orderForm.noItems
BSEE


BOILERS & HOT WATER


Taking the headache out of boiler commissioning


Andy Forrest, national sales manager at Ideal Commercial Boilers, looks at the various stages of commissioning, as well as the challenges and risks that are involved


or many working in the HVAC sector, commissioning presents itself as a costly and time sensitive process. However, it must be stressed to customers that the manufacturers’ commissioning process is a key part of a boiler installation. Commissioning engineers working for the manufacturer will ensure that the boilers have been installed to specific guidelines and are working correctly. In some cases, commissioning activates the warranty, which can be up to five years.


F


Challenges faced by commissioning engineers


One of the biggest challenges are boilers that have not been installed to the manufacturers’ guidelines. This can cause a whole host of problems, the main one being having to delay the commissioning process and, in some cases, wider building works until the issues are corrected and bought back into line with the manufacturers’ requirements. It could be that there is an inadequate supply of gas to the boilers. This can lead to a complete shutdown of the site and immediate action should be taken to rectify the situation. Alternatively, inadequate ventilation or the incorrect fitting of the flue can not only affect the efficiency of the boilers, it can also cause combustion problems and worse, carbon monoxide poisoning.


Finally, if the boilers cannot fire into high and low rate, they will not be able to provide enough heat load for warmth and/or hot water for the building.


Whether the commissioning process is missed out to cut costs, or down to a simple lack of time, it’s not uncommon for it to be overlooked. As a responsible manufacturer, Ideal Commercial took the bold step in 2018 to become the first manufacturer in the market to offer this service free of charge across most of its range, with just one simple online form to complete to book commissioning. This proved so popular that free commissioning has been extended into 2019.





The importance of pre­commissioning by the contractor


Fully


functioning boilers working uninterrupted at maximum efficiency is the aim of all new commercial boiler installations





As with any job, the contractor should ensure that sufficient pre-checks are carried out so that commissioning can take place on time and to budget. Just like checking a car over before it is sold to a customer, there is a need to ensure the basics have been checked. In the case of commissioning, this involves many small but vital steps. There needs to be a good amount of lighting and ventilation around the boiler. On a basic level service, engineers will need to have good lighting for future servicing or for emergency works on the boilers themselves. Ventilation is a crucial requirement. The threat of carbon monoxide poisoning is a big risk, so ensuring that the area of ventilation is correctly calculated at high and low levels is vital. This may seem like an obvious pre-check. However, during a busy build where boiler systems are often pushed to the back of the priority list in terms of installation, the basics of ventilation and lighting can be overlooked. To ensure that the project is on time and on budget, these checks need to be carried out.


Other important considerations include ensuring there is sufficient water pressure available, all flue, pipework and traps are in place and that sufficient fuel is available for the commissioning engineer’s visit. Very importantly, there needs to be sufficient system load available when the system is cold.


Carrying out the commissioning process


Having confirmed that the boilers have been installed correctly through pre-checks, the commissioning process can begin. The commissioning engineer from the boiler manufacturer will check that the boilers have been fitted to the specific requirements. Also, it’s worth noting that any deviance away from these requirements may result in any warranty becoming null and void. This is another reason why pre-checks are so important to the whole process. Gas piping - Checks on the gas piping will determine that they are correctly fitted, have all the correct isolation valves fitted and finally are operating at the correct pressure. It’s at this stage that the engineer will take combustion readings both at high and low fire to determine the correct pressure of the boiler. These readings will then be compared to the manufacturers’ recommendations and readings. A temperature differential will also be taken both at high and low fire. Positioning and integrity of the flue - Ensuring that the flue is clear, in the correct position and has adequate drain points, is one of the most important checks within the process. The integrity of the flue needs to be satisfactory (i.e. no open points or drains missing that can cause gas to leak out). Finally, the engineer will check that the type of flue used is of the correct classification. Combustion - There needs to be a temperature reading while checks for the high and low fire are taken. These temperatures need to be in line with the manufacturers’ recommended advice.


Free commissioning


Fully functioning boilers working uninterrupted at maximum efficiency is the aim of all new commercial boiler installations. Commissioning is a small but vital part of that process and should not be ignored, especially when it is available for free from Ideal Commercial.


Information about Ideal Commercial’s Free Commissioning Offer is available on the company’s website.


idealcommercialboilers.com


An Ideal Commercial Evomod installation at Newton Mearns Faith Campus near Glasgow


uHaving confirmed that the boilers have been installed correctly through pre­checks, the commissioning process can begin


12 BUILDING SERVICES & ENVIRONMENTAL ENGINEER FEBRUARY 2019


uAn Ideal Commercial Imax Xtra boiler installation being commissioned by an Ideal Boilers engineer


Read the latest at: www.bsee.co.uk


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48