BS EN ISO 10133:2017 ISO 10133:2012(E)
Annex A (normative)
Conductor requirements A.1 Table A.2 gives allowable maximum current ratings in amperes determined for 30 °C ambient temperature.
For conductors in engine rooms (60 °C ambient), the maximum current rating in Table A.2 shall be derated by the factors below.
Table A.1— Derating of conductors in engine rooms
Temperature rating of conductor insulation, °C
70
85 to 90 105 125 200
Multiply maximum current from Table A.2 by:
0,75 0,82 0,86 0,89 1
A.2 As a guideline: the voltage drop (E) at load, in volts, can be calculated using the following formula: E
=
where S l
0 0164, S
×× lL
is the conductor cross-sectional area, in square millimetres; is the load current, in amperes;
L is the length, in metres, of conductor from the positive power source to the electrical device and back to the negative source connection.
NOTE On a 12 V system an approximation of a 3 % drop can be obtained by the following:
S lL= × 20
10