This page contains a Flash digital edition of a book.
CPD PROGRAMME


Free cooling hybrid chillers There are a number of free cooling and adiabatic chillers on the market today (including the one illustrated in Figure 3). Some have screw compressor technology and inverter drives with electronically controlled heat rejection fans, to try to reduce the high start up currents and high part load running currents, while others incorporate the centrifugal, oil-free, magnetic bearing compressor package already mentioned. These have a combination of both free cooling for low ambient operation and adiabatic cooling for high ambient scenarios (hence, ‘hybrid’). The compressors have particularly low starting currents of about 5 amps per 350 kW cooling capacity. Seasonal EERs greater than 12 are easily achievable with these chillers, plus the higher chilled water temperatures allowed with the environmental envelope recommended for data centres. Table 1 gives an indication of the performance for the different options in which the chiller can operate. A further development to this hybrid


chiller is the addition of an actively managed evaporative system. Water is absorbed by a porous natural-fibre honeycomb array in the direct air path of the coils. The adiabatic cooling effectively reduces ambient temperatures in the immediate vicinity of coils by up to 10C, lowering condensing temperatures and significantly improving the chiller’s energy performance. The adiabatic advantage also increases chiller capacity at peak load conditions, enabling it to cope with high ambients that might otherwise overwhelm a standard chiller. The system can be set to activate automatically at a pre-determined external temperature. Water consumption is low. In UK conditions, £600 worth of water consumed a year results in energy savings worth some £8,000. In summary, the energy savings and improved performance also provide the following benefits: l Extended working life due to reduced compressor run-time;


l Reduced service and maintenance, due to reduced run-time;


l Payback time further reduced; and l Extended chiller capacity at peak load, enabling it to cope with extreme ambients that would defeat other chillers.


Floating head pressure The system operates with a floating head pressure, providing opportunities for savings not available to conventional


www.cibsejournal.com MW UV filter Cooling tower or adiabatic cooling unit CH.W Water cooled Turbocor high efficiency chiller Figure 4: Water cooled Turbocor chiller with adiabatic cooler


designs. Unlike standard chillers that have fixed head pressure, this centrifugal compressor package constantly self- regulates and optimises its performance in response to ambient conditions and load.


Water cooled options Where internal plant room space permits and/or noise design criteria is exceptional,


Duty (kW) Free cooling (kW) 900 900 900 900 900 900 900 900 900 900


0 0


229.6 460.6 870.8 900 900 900 900


894.6


Duty (kW) Free cooling (kW) 900 900 900 900 900 900 900 900 900


0 0 0


344.4 694.4 900 900 900 900


Duty (kW) Free cooling (kW) 900 900 900 900 900 900 900


0 0 0 0 0 0 0


water cooled versions of these low energy chillers can be used, matched with closed circuit cooling towers or adiabatic coolers. Figure 4 illustrates a typical system. Although doubling up on plant items, water cooled versions of the oil-free technology can achieve ESEERs (European Seasonal Energy Efficiency Ratio) in excess of 10, while using the higher allowable chilled water temperatures and capitalising on adiabatic cooling at higher ambient conditions. Centrifugal, oil-free chiller packages up to 2.4 megawatts (MW) are available. Lower condensing water temperatures can be achieved with this equipment and will produce a very efficient overall cycle. Lower starting and running currents for this type of equipment can also reduce infrastructure cabling cost and maximum demand charges, as well as running cost.


© Terry Welch and Steve Chaplin (Klima-Therm) 2012


References


1. ASHRAE TC 9.9 white paper 2011 Thermal Guidelines for Data Processing Environments


2. Fresh Approach, CIBSE Journal April 2011, Marcus O'Brien


3. Klima-Therm 2011 Adiabatic Free Cooling Options for Data Centre


TMA 3A900B EC FC – Adiabatic system and free cooling EER (–) 4.8


5.45 8.73


12.33 22.96 22.96 28.32 75.63


142.86 257.14


39.2 39.2


31.78 11.9 6.3 3.5


35 30 26 22 15 12 10 5 0


-5


TMA 3A900B EC FC – Adiabatic/dry mode only and free cooling EER (–) 4.43 4.8


5.45


10.39 16.95 28.32 75.63


142.86 257.14


187.4 165.2 86.6 53.1


31.78 11.9 6.3 3.5


35 31 26 20 15 10 5 0


-5


TMA 3A900B EC FC – Spray/dry mode without free cooling EER (–) 4.43 4.8


5.45 7.06 9.01 9.94


10.23


187.4 165.2


127.48 99.94 90.56 88


Et. glycol 20%; RWT= 26C; LWT= 20C; Reference capacity 900 kW Table 1: Typical energy savings and EERs for hybrid chiller


April 2012 CIBSE Journal 53


35 31 26 18 10 0


-5


Input (kW) Ambient temp. (C) Working condition 187.4 165.2 103.1 73


Evaporative cooling Evaporative cooling Evaporative cooling Evaporative cooling Evaporative cooling Dry mode Dry mode Dry mode Dry mode Dry mode


Input (kW) Ambient temp. (C) Working condition 203


Dry mode Dry mode Dry mode Dry mode Dry mode Dry mode Dry mode Dry mode Dry mode


Input (kW) Ambient temp. (C) Working condition 203


Dry mode Dry mode Dry mode Dry mode Dry mode Dry mode Dry mode


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68