Integrated Free-Cooling Systems for Heat Management Blowing Hot and Cold By Paul Oliver, Sales Director, Airedale


Rising data centre temperatures must be stabilised to ensure that the IT equipment will operate reliably, yet they present significant opportunities to reduce the cost of running the cooling equipment and increase the potential for free-cooling.


Development of server technology is raising the thermal envelopes of data centres. Traditionally, 2kW of energy per rack would reject air into the room at around 28°C. A 42U rack with six fully populated blade enclosures can reject up to 30kW of heat into the room at a temperature of 47°C.


Data centre power consumption in the UK is estimated at between 2.2% and 3.3% of total UK power consumption. Cooling is currently estimated to represent between 30% and 50% of power consumption within a data centre. Cooling in data centres in the UK has an annual carbon footprint exceeding 1.75 million tonnes of CO2


. Rising temperatures


Many data centres still operate at around 20°C and 22°C, but as server technology advances and servers generate more heat, they also become capable of running at higher temperatures. Modern servers are capable of running at 35°C. Whilst nobody wants to run servers


near that temperature, ASHRAE (the American Society of Heating, Refrigerating, and Air-Conditioning Engineers) now recommend an operating temperature in data centres of up to 27°C. Running data centres at 27°C would offer substantial benefits to the operator. The efficiency of cooling equipment


would be increased, as it runs more efficiently at the higher return air temperature of 27°C. Opportunities to use free-cooling would also be increased, as there are more days when the ambient outdoor temperature is cooler than 27°C compared with days when it is below 20°C. Where hotspots exist, some operators


choose to cope with them by cooling the entire data centre instead of simply cooling only the affected areas. In doing so, operators will reduce the operating efficiency of the cooling system and destroy any free-cooling potential. Higher room temperatures can be


offset by increasing the chilled water temperatures. The controls system will monitor the room load via sensors and automatically adjust chilled water setpoints to match this load. By raising


52 NETCOMMS Volume I, Issue 4 2011 Ambient temperature in the UK.


these setpoints, plant energy efficiency and the free-cooling threshold can be significantly increased. A 1°C increase in fluid temperature can give an 8.5% increase in chiller energy efficiency.


Using ambient temperature


Free-cooling works by taking advantage of the ambient temperature being cooler than the temperature inside the room being cooled. In a data centre cooled by CRAC units and a chiller system, warm air is returned to the CRAC units and heat within the air is given up to the cooler water being circulated through the CRAC units. Now warmer, the water carries the heat externally to the chillers which cool the water without the need for mechanical refrigeration, in a similar way in which the radiator in a car cools the liquid from a car engine. The liquid, now cool, returns to the CRAC units and the cycle begins all over again. The diagram above shows the


distribution of hourly UK ambient temperature. A typical air conditioning system operating at 22°C will require chilled water at around 7°C. To achieve this kind of temperature using free-cooling, the ambient temperature would need to be cooler than the water by about 5°C, i.e. 2°C. The number of hours at 2°C or below in the UK represents about 7% of the UK ambient year.


If we shift the operating temperatures


upwards by 5°C, making the room 27°C, we can lift all the operating temperatures of the cooling fluid by the same amount to achieve the same capacity. Now, the ambient temperature need only be 7°C to satisfy full free-cooling – the number of hours at 7°C or below in the UK represents 30% of the UK ambient year. The opportunity for free-cooling


is present whenever the ambient temperature is below the room operating temperature, i.e. 98% of the UK ambient year. There are a huge number of ambient hours around the middle of the bell curve, which are not being captured by most free- cooling systems. In systems with non-concurrent


free-cooling, when free-cooling cannot deliver 100% of the required capacity, free-cooling is sacrificed and replaced by mechanical cooling. There is no ability to mix free-cooling and mechanical cooling. Thus, as soon as the ambient temperature reaches a point where it cannot satisfy the entire cooling demand, all cooling is mechanical, none is ‘free’. The best systems bring together


free-cooling and mechanical cooling simultaneously, enabling free-cooling to be captured whenever the ambient is below the return water temperature.


www.netcommseurope.com


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60