categories, and/or there are different technical installations serving different parts of the building or if the internal gains are significantly higher or lower in different parts of the building.

With regard to solar gains, the procedure for the energy calculation NS 3031:2007 specifies that; “in cases where parts of a building are subject to high solar heat gains, whereas other parts of the building are subject to moderate solar heat gains, the building must be divided into relevant zones for the energy demand calculations. For buildings with moderate fenestration, and efficient outside shading, it is sufficient to calculate the building as one zone”.

In the case of large window and glass areas and/or little efficient sun shading, the building must be divided into zones based upon the following > When the product of area of windows, doors and glass (γsol), divided by the conditioned floor area and the total solar energy transmittance

for window and shading, gt, supersedes 5 % (γsol/ tg > 5 %), the

building shall be divided in at least three calculation zones -One zone with façade exposed to the sun (orientation south, southeast or southwest) -One zone with little exposure to the sun (north, northeast, northwest)

-One zone in the middle of the building;

> The depth of zones with facades exposed to the sun and facades with little exposure to the sun can be set to 4 to 5 meters. Where there is a very ”slim” building design, overall depth less than 10 meters, the number of zones can be reduced to two, one exposed to the sun and one with no exposure to the sun.

> Conservatories, atriums, glass buildings or similar with all facades mainly constructed of glass should be calculated as a single zone

> Total solar energy transmittance for window and shading is defined in the detailed calculation procedures. With variable total solar energy transmittance on different facades, the values for level of exposure to the sun must be used (south, southeast, southwest)

NOTE: For buildings where the product of area of windows, doors and glass, γsol, and the total solar energy transmittance for window and sun shading gt, is less 5 % (γsol/gt < 5 %), there will normally be no need for zoning due to sun contribution.

EPBD Buildings Platform > P85_EN_Norway-June 2008

Page 157

5 Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72  |  Page 73  |  Page 74  |  Page 75  |  Page 76  |  Page 77  |  Page 78  |  Page 79  |  Page 80  |  Page 81  |  Page 82  |  Page 83  |  Page 84  |  Page 85  |  Page 86  |  Page 87  |  Page 88  |  Page 89  |  Page 90  |  Page 91  |  Page 92  |  Page 93  |  Page 94  |  Page 95  |  Page 96  |  Page 97  |  Page 98  |  Page 99  |  Page 100  |  Page 101  |  Page 102  |  Page 103  |  Page 104  |  Page 105  |  Page 106  |  Page 107  |  Page 108  |  Page 109  |  Page 110  |  Page 111  |  Page 112  |  Page 113  |  Page 114  |  Page 115  |  Page 116  |  Page 117  |  Page 118  |  Page 119  |  Page 120  |  Page 121  |  Page 122  |  Page 123  |  Page 124  |  Page 125  |  Page 126  |  Page 127  |  Page 128  |  Page 129  |  Page 130  |  Page 131  |  Page 132  |  Page 133  |  Page 134  |  Page 135  |  Page 136  |  Page 137  |  Page 138  |  Page 139  |  Page 140  |  Page 141  |  Page 142  |  Page 143  |  Page 144  |  Page 145  |  Page 146  |  Page 147  |  Page 148  |  Page 149  |  Page 150  |  Page 151  |  Page 152  |  Page 153  |  Page 154  |  Page 155  |  Page 156  |  Page 157  |  Page 158  |  Page 159  |  Page 160  |  Page 161  |  Page 162  |  Page 163  |  Page 164  |  Page 165  |  Page 166  |  Page 167  |  Page 168  |  Page 169  |  Page 170  |  Page 171  |  Page 172  |  Page 173  |  Page 174  |  Page 175  |  Page 176  |  Page 177  |  Page 178  |  Page 179  |  Page 180  |  Page 181  |  Page 182  |  Page 183  |  Page 184  |  Page 185  |  Page 186  |  Page 187  |  Page 188  |  Page 189  |  Page 190  |  Page 191  |  Page 192  |  Page 193  |  Page 194  |  Page 195  |  Page 196  |  Page 197  |  Page 198  |  Page 199  |  Page 200  |  Page 201  |  Page 202  |  Page 203  |  Page 204  |  Page 205  |  Page 206  |  Page 207  |  Page 208  |  Page 209  |  Page 210  |  Page 211  |  Page 212  |  Page 213  |  Page 214  |  Page 215  |  Page 216  |  Page 217  |  Page 218  |  Page 219  |  Page 220