EC controller
Connecting the EC controller – example of a fan with MODBUS RTU compatibility
Stand-alone control device for refrigeration and air-conditioning technology in conjunction with the The EC controller functions as a stand-alone control device for fan networks in combination with external sensors. Factory default applications ensure
corresponding sensors. Using the controlled 0–10 V output or RS485 MODBUS RTU connection, easy commissioning – connecting a computer or other software-supported devices is not necessary. For programming new applications and for
ebm-papst fans with a corresponding input can be triggered. The function includes multifunctional monitoring, an integrated keypad control with LCD display replaces the external input devices.
pressure and temperature control as well as display and entry of various parameters. The integrated
LCD display provides easy operation across multiple levels. Note for large systems: After 31 fans, a repeater can be installed in order to connect another 31 fans.
Nominal data
Type CCC000-AD06-02
Nominal voltage V 1~200–480
Frequency Hz 50/60
Power consumption W 15
Power supply for sensor VDC 24
1
Output current mA 120
External sensor
Permitted ambient temperature °C 0 to +60
Pressure sensor,
Permitted storage temperature °C –20 to +60
temperature sensor
Dimensions mm 200 x 167 x 76
Specifications subject to change!
RS485 MODBUS RTU
or 0–10 V
Inputs/outputs – 24 V power supply for sensors
– Analogue inputs for connecting up to 2 sensors per type
– 4 digital inputs
Power supply
– 2 programmable relay outputs, 2 voltage outputs 0–10 V
2
– RS485 MODBUS RTU
Applications – Temperature control, standard
EC controller
– Pressure control of ventilation systems, condensers, 2-circuit condensers
– Pressure control, ambient temperature-compensated
These applications are the factory defaults. Other applications can be programmed individually.
Sensors – Temperature sensor KTY 10-6 (R25 = 2 kΩ), NTC 103AT (R25 = 10 kΩ)
– Pressure sensor 0 to 100/200/500/1000 Pa (0–10 V output), 0 to 30 bar (4–20 mA output)
– ebm-papst temperature sensors, Art. No. 50003-1-0174 and 50005-1-0174
1 Example terminal assignment for fan 2 Example terminal assignment – EC controller
– Other sensors can be programmed individually KL1
1 2 3
Menu languages German/Swedish/Danish/English (factory setting)
L1
N/L2
PE
Housing Plastic housing
Product conforming CE
KL3 KL2 PE KL1 KL2 KL3
to standard
Type of protection IP 54 (acc. to DIN EN 60529)
Din2 Din3 GND
Ain2 I
Aout GND GND GND GND GND GND
D1 D2 D3 D4
Ain2 U
+20V
RSA RSA GND GND
Relais 1 Relais 2
0–20 mA 0–20 mA
EMC Acc. to EN 61000-6-3 and EN 61000-6-2
p p p p
RSA RSB
m m m
GND
Installation Vertical wall mounting, direct solar radiation and installation on vibrating substrate is not permitted.
Ain1 U
+10V Ain1 I
Din1
NO
COM
NC PE L1 L2 L3
Relais 1 Relais 2
Te Te +24 V +24 V
GND GND GND GND RSB RSB
m
Te Te
0–10 V E 0–10 V E 0–10 V E 0–10 V E
Electrical leads via terminal strips
18 19
Page 1 |
Page 2 |
Page 3 |
Page 4 |
Page 5 |
Page 6 |
Page 7 |
Page 8 |
Page 9 |
Page 10