This page contains a Flash digital edition of a book.
7


6.5 6


5.5 5


4.5 4


3.5 3


0 2 4 Month


Figure 3: The EER value trend of a chiller without free cooling when operating with a fixed water outlet temperature


6 8 December EER January November March October July


8


7.5 7


6.5 6


5.5 5


Outlet temperature


4.5 4


0 5 10 15 Time


Figure 4: The outlet water temperature trend. Inverter control achieves much greater water accuracy than is possible through control with a standard screw compressor


20 25 30


screw compressors can attain COP> 8 and EER > 7. Figure 3 shows the EER value trend of a


chiller without free cooling when operating with a water outlet temperature of 5C. This example chiller is designed for 680 kW at full load. During the warmer months of the season (June-August) the required load is 100%, whilst during the colder period (November-March), when ambient temperature is much lower, the chiller load is estimated between 50% and 60%. In the hotter months, during the most


demanding ambient conditions, EER has a minimum value of 4, whilst when the chiller load is around 60%, the EER values are typically between 6 and 7, much higher than a standard chiller. All these values relate to the maximum ambient temperature for each month, so these EER are considered a minimum. Figure 4 shows the outlet water temperature trend. Inverter control achieves much closer water temperature control than is possible with a standard screw compressor. In this example the water temperature fluctuation is only +/- 0.5C. The set point value is established more rapidly than might be expected using traditional chiller control. The ESEER is the EU index used to


classify chiller performance (and differs slightly from the UK SEER that typically takes more account of peak load operation); and for chillers with inverter control led screw compressor (and variable volume index, Vi), the increase for this example ESEER is around 15%.


www.cibsejournal.com


Inverter controlled air cooled condenser fans Inverters are also applicable to axial fans, and so can control the air circulated through the condensers in air cooled chillers in place of simple on/off or step control to steadily reduce the air flow and achieve improved condenser control. The benefits will not only be in improving the efficiency ratios by around 10%, but also by reducing noise levels for significant periods of time when the system is running at part load (typically up to 6dBA).


Conclusions There are many opportunities to apply innovative solutions to reduce the absorbed power requirements of refrigeration hardware in commercial air conditioning and data centre facilities. The optimum operation of refrigeration equipment at part loads is especially significant in conditions where the average annual ambient air temperatures are between 5C and 20C – typical of the vast majority of European conditions. For even lower ambient temperatures, the combination of inverter technology, coupled with that of free cooling – whereby chilled water can be produced using only fans’ energy – can be effectively used to produce chiller units with even greater efficiencies than previously considered possible. CJ


l Maurizio BurBa is managing director of Hitema. www.hitema.it A version of this article first appeared in the October 2011 edition of REHVA Journal. www.rehvajournal.com


Inverter control achieves much closer water temperature control than is possible with a standard screw compressor


February 2012 CIBSE Journal 45


EER


Temperature ( C)


Page 1  |  Page 2  |  Page 3  |  Page 4  |  Page 5  |  Page 6  |  Page 7  |  Page 8  |  Page 9  |  Page 10  |  Page 11  |  Page 12  |  Page 13  |  Page 14  |  Page 15  |  Page 16  |  Page 17  |  Page 18  |  Page 19  |  Page 20  |  Page 21  |  Page 22  |  Page 23  |  Page 24  |  Page 25  |  Page 26  |  Page 27  |  Page 28  |  Page 29  |  Page 30  |  Page 31  |  Page 32  |  Page 33  |  Page 34  |  Page 35  |  Page 36  |  Page 37  |  Page 38  |  Page 39  |  Page 40  |  Page 41  |  Page 42  |  Page 43  |  Page 44  |  Page 45  |  Page 46  |  Page 47  |  Page 48  |  Page 49  |  Page 50  |  Page 51  |  Page 52  |  Page 53  |  Page 54  |  Page 55  |  Page 56  |  Page 57  |  Page 58  |  Page 59  |  Page 60  |  Page 61  |  Page 62  |  Page 63  |  Page 64  |  Page 65  |  Page 66  |  Page 67  |  Page 68  |  Page 69  |  Page 70  |  Page 71  |  Page 72